39ECL-PTU-207 Preloaded Applications
SensorSleepTime (ConstantNum8)
This variable is used to configure the sensor sleep time of the EC-Smart-Comfort sensor. If set to 0,
the sensor sleep time is disabled
ID Units Valid Range Default Value
Constant Numeric 8 seconds N/A 0 second
SlaveTempDelta (ConstantNum14)
This variable is used to configure the minimum temperature variation before updating the nvoSlave-
Info.SpaceTemp value.
ID Units Valid Range Default Value
Constant Numeric 14 Degrees-celsius (°C) N/A 0,1 °C
SlaveDelayMotion (ConstantNum15)
This variable is used to configure the motion stop delay before updating the nvoSlaveInfo.Motion value
ID Units Valid Range Default Value
Constant Numeric 15 seconds N/A 10 seconds
ChangeOverCoolOn (ConstantNum16)
This variable is used to configure the water temperature below which 2 pipes change-over systems
are considered to be in cooling mode.
ID Units Valid Range Default Value
Constant Numeric 16 Degrees-celsius (°C) N/A 16 °C
ChangeOverCoolOff (ConstantNum17)
This variable is used to configure the water temperature above which 2 pipes change-over systems
are considered to be in heating mode.
ID Units Valid Range Default Value
Constant Numeric 17 Degrees-Celsius (°C) N/A 20 °C
Variables

Table of Contents

Other manuals for Distech Controls ECL-PTU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECL-PTU Series and is the answer not in the manual?

Distech Controls ECL-PTU Series Specifications

General IconGeneral
BrandDistech Controls
ModelECL-PTU Series
CategoryController
LanguageEnglish

Related product manuals