56 ECL-PTU-207 Preloaded Applications
Minimum and Maximum Fan Configuration
The following table describes the minimum and maximum fan configuration.
Figure23: Minimum and Maximum Fan Configuration
Parameter Description
Maximum Discharge Air Setpoint Set the maximum discharge air setpoint.
Minimum Discharge Air Setpoint Set the minimum discharge air setpoint.
Fan Configuration
The following table describes the fan configuration.
Figure24: Fan Configuration
Parameter Description
Control Mode
Continuous – Fan continuously operating
Cycle – Fan cycling based on heating/cooling load
Con Cycle – Fan continuously operating in occupied mode and cycling during unoccupied
periods
Cycle Heat – Fan cycling based on heating load only
Cycle Cool – Fan cycling based on cooling load only
Fan Off Delay Amount of time before the fan enters standby.
Using the dcgfxApplications