32 ECL-PTU-207 Preloaded Applications
nvoTerminalLoad (nvoFP06)
This output indicates the current heat/cool energy demand of the unit.
Positive values indicate that cooling energy is required (or in use) by the space comfort controller,
while negative values indicate that heating energy is required (or in use) by the space comfort con-
troller.
This reports the output of the heating/cooling control algorithm.
ID Units Valid Range Default Value
nvoFP06 SNVT_lev_percent N/A N/A
nvoSpaceRH (nvoFP07)
This output network variable indicates the space humidity in percent, if the Space Comfort Controller
Device has an Allure EC-Smart-Vue sensor with humidity. If not used, this variable output is 163.835%
ID Units Valid Range Default Value
nvoFP07 SNVT_lev_percent N/A N/A
nvoSpaceCO2 (nvoFP09)
This output network variable indicates the space CO2 concentration in ppm, if the Space Comfort
Controller Device has a locally wired CO2 sensor.
If a valid value is received by nviSpaceCO2, this value has priority over the local input or the Allure
EC-Smart-Vue sensor with CO2 sensor.
If not used, this variable output is 65535 ppm.
ID Units Valid Range Default Value
nvoFP09 SNVT_ppm N/A N/A
nvoEnergyHoldOff (nvoFP10)
This output indicates the actual Energy Hold Off state of the device.
If the variable nviWindowContact is connected, the Energy Hold Off will be set to 1,100 if a window is
open within the zone.
The hard-wired window contact input will also affect this variable.
ID Units Valid Range Default Value
nvoFP10 SNVT_swith N/A N/A
nvoLocalSpaceTemp (nvoFP11)
This output network variable provides the value of a local hardwired space temperature input.
This is useful for averaging several controllers’ data together when controlling a large space.
Refer to nviSpaceTempAvg for information on how to average multiple controllers together.
This output value will output one of the following using this priority order:
£ SI3 Space Temperature
£ EC-Smart-Vue temperature
£ EC-Remote Space Temperature
£ SI3 Return Temperature
£ EC-Multi-Sensor Temperature
ID Units Valid Range Default Value
nvoFP11 SNVT_temp_p N/A N/A
Variables