81ECL-PTU-207 Preloaded Applications
CLG T - Cooling Valve Type
Parameter Default Valid
Choices
Description
CLG TYPE
(EC7)
0 UNUSED Cooling valve is not used
X 1 0-10V 0-10V cooling valve only is used
2 THERMAL Thermal and 0-10V cooling valve are used
3 ON_OFF On/Off and 0-10V cooling valve are used
4 FLOATING Floating and 0-10V cooling valve are used
Table17: Cooling Valve Type
CLG N - Cooling Valve Polarity
Select Normally Open or Normally Closed depending on your system.
HTG T - Heating Valve Type
Parameter Default Valid
Choices
Description
HTG TYPE
(EC8)
0 UNUSED Heating valve is not used
X 1 0-10V 0-10V heating valve only is used
2 THERMAL Thermal and 0-10V heat valve are used
3 ON_OFF On/Off and 0-10V heat valve are used
4 FLOATING Floating and 0-10V heat valve is used
Table18: Heating Valve Type
HTG N - Heating Valve Polarity