39ECLYPSE Connected Thermostat (ECY-STAT)
EC-Net-Based Centralized Credential Authentication
The credential database is centralized in an EC-Net station to authenticate login requests made by all
other subscribed ECLYPSE controllers.
EC-gfxProgram
EC-Net
RADIUS A
ECLYPSE
Controller B
Cache B
ECLYPSE
Controller A
Cache A
1 2 2
3
EC-Net
FOX
3
Figure23: EC-Net-Based Centralized Credential Authentication
This authentication method has the following components.
Component Description
Login Credential 1
This is the login credential used by an EC-
gfx
Program user to connect to the EC-Net station. This
credential is managed in the EC-Net User Service.
Login Credential 2
This is the login credential used by an EC-
gfx
Program user to connect to any ECLYPSE controller.
This credential is managed in the EC-Net User Service.
Login Credential 3
This is the login credential used by the EC-Net station’s RestService to connect to any ECLYPSE
controller. To program an ECLYPSE controller with EC-
gfx
Program through EC-Net, the RestService
must be configured on the EC-Net station with a login credential to all ECLYPSE controllers. This
credential is managed in the EC-Net User Service.
RADIUS Server A
Credential Database
This is EC-Net station UserService credential database that is also a RADIUS Server credential
database.
If EC-
gfx
Program users are to connect to this controller through the EC-Net station, this credential
database must have the credentials for EC-Net station’s RestService. This credential database must
also have the credentials for each user that will login to ECLYPSE controller A or B (for example,
administrators, direct connection EC-
gfx
Program users, ENVYSION users, etc.).
Note that other EC-Net stations can use FOX protocol to authenticate users on those stations.
Credential Databases
Cache A and B
These are ECLYPSE controllers’ cached credential databases. If the connection to the EC-Net
station’s RADIUS Server is lost, users that have previously authenticated themselves with EC-Net
station’s RADIUS Server credential database on a given controller will still be able to login to those
controllers as their credentials are locally cached.
Supported RADIUS Server Architectures

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECLYPSE ECY-STAT and is the answer not in the manual?

Distech Controls ECLYPSE ECY-STAT Specifications

General IconGeneral
BrandDistech Controls
ModelECLYPSE ECY-STAT
CategoryThermostat
LanguageEnglish

Related product manuals