USER MANUALRelease 1.2 of 01/01/2010 Page 27 of 191
Version: 02/03/2010
SP 4
Offset NTC probe remote terminal n° 1
-12.0
-21
12.0
21
°C
°F
Dec
int
SP 5
Offset NTC probe remote terminal n° 2
-12.0
-21
12.0
21
°C
°F
Dec
int
Working mode
SP 6
Working mode
0= cooling / heating
1= cooling / heating
0
1
Cooling / heating mode selection
SP 7
Cooling / heating mode selection from:
0= keyboard
1= digital input
2= analogue input (automatic changeover)
0
2
Automatic change over
Parameter
Description
min
max
udm
Resolution
SP 8
Cooling / heating mode automatic changeover set point
-50.0
-58
110
230
°C
°F
Dec
int
SP 9
Cooling 7 heating mode automatic changeover differential
0.1
1
25.0
45
°C
°F
Dec
int
Measurement unit selection
SP 10
°C or °F selection
0= °C / °BAR
1= °F / °psi
0
1
Network frequency selection
SP 11
Network frequency selection
0= 50 Hz
1= 60 Hz
2= continuous power supply
WARNING with SP 11 = 2 the PWM proportional outputs for fan speed control
are not managed (network frequency alarm is off)
0
2
Serial address
SP 12
Serial address
1
247
SP 13
Firmware release
SP 14
Eeprom parameter map
Password
SP 15
Password Level 2 (Pr2)
0
9999
SP 16
Password Level 3 (Pr3)
0
9999
Dynamic set-point
Parameter
Description
min
max
um
Resolution
Sd 1
Dynamic set-point max increase in cooling mode
Maximum variation of the work set-point in cooling mode.
-50.0
-58
110
230
°C
°F
Dec
int
Sd 2
Dynamic set-point max increase in heating mode
Maximum variation of the work set-point in heating mode.
-50.0
-58
110
230
°C
°F
Dec
int
Sd 3
Dynamic set-point external air temperature set in cooling mode
-50.0
-58
110
230
°C
°F
Dec
int
Sd 4
Dynamic set-point external air temperature set in heating mode
-50.0
-58
110
230
°C
°F
Dec
int
Sd 5
Dynamic set-point external air temperature differential in cooling mode
-50.0
-58
110
230
°C
°F
Dec
int
Sd 6
Dynamic set-point external air temperature differential in heating mode
-50.0
-58
110
230
°C
°F
Dec
int
Energy saving
Parameter
Description
min
max
um
Resolution
ES 1
Start of working time band n°1 (0÷24)
0
24.00
Hr
10 Min
ES 2
End of working time band n°1 (0÷24)
0
24.00
Hr
10 Min
ES 3
Start of working time band n°2 (0÷24)
0
24.00
Hr
10 Min
ES 4
End of working time band n°2 (0÷24)
0
24.00
Hr
10 Min
ES 5
Start of working time band n°3 (0÷24)
0
24.00
Hr
10 Min
ES 6
End of working time band n°3 (0÷24)
0
24.00
Hr
10 Min
ES 7
Monday energy saving time band definition
0 = None
1 = Time band 1
2 = Time band 2
3 = Time bands 1 & 2
4 = Time band 3
5 = Time band 1 & 3
6 = Time band 2 & 3
7 = All time bands
0
7
ES 8
Tuesday energy saving time band definition
0
7
ES 9
Wednesday energy saving time band definition
0
7
ES 10
Thursday energy saving time band definition
0
7
ES 11
Friday energy saving time band definition
0
7