USER MANUALRelease 1.2 of 01/01/2010 Page 28 of 191
Version: 02/03/2010
ES 12
Saturday energy saving time band definition
0
7
ES 13
Sunday energy saving time band definition
0
7
ES 14
Energy saving set increase in cooling mode
-50.0
-58
110
230
°C
°F
Dec
int
ES 15
Energy saving differential in cooling mode
0.1
0
25.0
45
°C
°F
Dec
int
ES 16
Energy saving set increase in heating mode
-50.0
-58
110
230
°C
°F
Dec
int
ES 17
Energy saving differential in heating mode
0.1
0
25.0
45
°C
°F
Dec
int
ES 18
Monday automatic ON/OFF time band definition
0
7
ES 19
Tuesday automatic ON/OFF time band definition
0
7
ES 20
Wednesday automatic ON/OFF time band definition
0
7
ES 21
Thursday automatic ON/OFF time band definition
0
7
ES 22
Friday automatic ON/OFF time band definition
0
7
ES 23
Saturday automatic ON/OFF time band definition
0
7
ES 24
Sunday automatic ON/OFF time band definition
0
7
ES 25
Unit maximum working time in OFF from RTC if forced in ON from key
0
250
Min
10 Min
Compressor
Parameter
Description
min
max
um
Resolution
CO 1
Compressor minimum ON time
Compressor ON time after its activation even if the demand is OFF
0
250
Secs
10 secs
CO 2
Compressor minimum OFF time
Compressor OFF time after its deactivation, even if demand is ON. The
relevant LED flashes during this period.
0
250
Secs
10 secs
CO 3
Minimum time between following activations of the same compressor
0
250
Secs
10 secs
CO 4
Switch-ON delay between 2 compressors/steps
Minimum delay between activation of two following capacity steps
(compressor or unloader). The compressor icon flashes during this period
(only for compressor)
1
250
Secs
CO 5
Switch-OFF delay between 2 compressors/steps
Establishes the switch-off delay between the two capacity steps (compressors
or unloaders)
1
250
Secs
CO 6
Maximum Delay between compressor ON and compressor maximum capacity
0
250
Secs
CO 7
Delay between unit power ON and compressor ON
Delays the activation of all outputs to distribute the mains power consumption
and protects the compressor/s from repeated switch-on in the case of
frequent power supply failures
0
250
Secs
10 secs
Compressors Unloaders
CO 8
Unloaders activation mode (see relevant chapter)
0= ON/OFF activation with steps
1= continuous activation with direct action steps
2= continuous activation with inverse action steps
3= Continuous direct global step activation
0
3
CO 9
Compressor minimum capacity enabling / unloaded compressor start
0 = Enables minimum power only at compressor start-up (start-up with
minimum capacity / idle running valve in OFF with compressor off )
1 = Enables minimum power at compressor start-up and in temperature
control mode (start-up with minimum capacity/idle running valve in OFF with
compressor OFF)
2 = Screw compressors: enables the minimum power only at compressor
start-up (start-up with minimum capacity / idle running valve in ON with
compressor off )
3 = Screw compressors: enables the minimum power at compressor start-up
and in temperature control mode (start-up with minimum capacity/idle running
valve in ON with compressor off )
0
3
Intermittent valve function
CO 10
Screw comp. intermittent valve relay ON time. If the value of the parameter is
0 the function is disabled
0
250
Secs
CO 11
Screw comp. intermittent valve relay OFF time
0
250
Secs
Compressor start-up
CO 12
Compressor start-up
0= direct (see compressors start-up)
1= part winding (see compressors start-up)
2= star delta (see compressors start-up)
0
2
CO 13
If CO10= 1 part - winding start-up time. Varies the coupling of the two different
relays that feed the two motor windings.
If CO10= 2 Star delta start-up time. Varies the simultaneous working time of
the line 1 relay and the relay that closes the star centre connection. (see
part winding / star delta start-up par.)
0
100
0.1 secs
CO 14
If CO10= 2 Star delta start-up time. Varies the time from the release of the
star centre to the coupling of the line n° 2 relay (see star delta start-up par.)
0
50
0.01 secs
CO 15
Switch-on time with gas by-pass valve/compressor idle running valve (see
unloaders working)
0
250
secs