Pumps Enabling and Rotation:
0 = Single Pump – No Rotation;
1 = 2 Pumps – Manual Rotation;
2 = 2 Pumps – Rotation according to starts;
3 = 2 Pumps –Rotation according to running hours;
4 = 2 Pumps –Rotation according to starts and running hours
Pumps Manual Inversion:
0 = Pump 1 On;
1 = Pump 2 On
Number of running hours for condenser pump forced rotation
Simultaneous pumps working time after forced rotation
Condenser water pump working mode in case of anti-freeze alarm
Determines the condenser water pumps working mode in case of antifreeze
alarm when the device is OFF or in stand-by mode
0= always OFF
1 = ON the temperature control demand
Antifreeze alarm control probe
0 = disabled
1 = Common condenser water inlet probe
2 = Common and circuits 1 / 2 condenser water inlet probe.
3 = Common and circuits 3 / 4 condenser water inlet probe
4 = Circuits 1 / 2 condenser water outlet probe
5 = Circuits 3 / 4 condenser water outlet probe
6 = All circuits condenser water outlet probe
7 = All circuits condenser outlet and common outlet water probe
8 = External air temperature
Condenser water pump activation set-point
Condenser water pump deactivation differential
Condenser water pump maintenance request
Main condenser pump maintenance period (see maintenance request function
chapter)
Support condenser pump maintenance period
Pump down function
Pump down
Pump down function (see relevant chapter)
0= function disabled
1= Pump down only at stop
2= Pump down at start and stop
3= Pump down only at stop in cooling mode
4= Pump down at start and stop in cooling mode
Pump down pressure set (see pump down chapter)
Pump down pressure differential (see pump down chapter)
Maximum pump down time at start and stop
Pump down at start time
0 = function disabled
Pump down at stop time
0 = function disabled
Maximum number of pump down alarm at stop per hour.
Above this limit the alarm is recorded and shown on the display, the alarm
relay and the buzzer are activated
Reset is always manual if Pd7 = 0
Reset is always automatic if Pd7 = 60
Reset switches from automatic to manual if Pd7 is between 1 and 59
Maximum number of pump down alarm at start per hour.
Above this limit the alarm is recorded and the alarm relay and the buzzer are
activated
Reset is always manual if Pd8 = 0
Reset is always automatic if Pd8 = 60
Reset switches from automatic to manual if Pd8 is between 1 to 59 depending
Pd9 configuration
Manual reset enabling for pump down at start alarm
0= Automatic reset even if the maximum number of occurrence /hour Pd8 is
reached
1= Manual reset if the maximum number of occurrences /hour Pd8 is reached
Unloading Function
High evaporator water inlet temperature