USER MANUAL – Release 1.2 of 01/01/2010 Page 32 of 191
High evaporator water inlet temperature unloading function set-point in
cooling mode
High evaporator water inlet temperature unloading function differential in
cooling mode
High evaporator water inlet temperature unloading function activation delay
High evaporator water inlet temperature unloading function maximum
activation time
High evaporator water inlet temperature unloading function control probe
Low evaporator water outlet temperature
Low evaporator water outlet temperature unloading function set-point
Low evaporator water outlet temperature unloading function differential
Low evaporator water outlet temperature unloading function activation delay
Low evaporator water outlet temperature uloading function maximum
activation time
Low evaporator water outlet temperature unloading function control probe.
High condensing pressure/ temperature in Cooling and Heating mode
High condensing pressure/temperature unloading function set point
High condensing pressure/temperature unloading function differential
Low evaporating pressure – active on all functions
Low evaporating pressure unloading function set point
Low evaporating pressure unloading function differential
Low evaporating pressure maximum activation time
Max number of capacity steps per circuit during unloading working mode
Minimum working time in unloading after function activation (only for
compressor with unloaders)
Outdoor fan speed control
Fan speed control
0 = Not managed
1 = always on
2 = ON/OFF activation with steps
3 = ON/OFF continuous activation with steps (see relevant chapter)
4 = proportional speed regulator
Outdoor fans activation
0 = depending on the compressor
1 = independent from the compressor
Outdoors fans activation time at full speed at start. Fans are activated at full
speed at start for the FA03 period independently from the conditions. After
this period the fan speed modulates according to the conditions
Fan phase displacement analogue output number 5
Fan phase displacement analogue output number 6
Outdoor fan distribution (see relevant chapter)
0= unique (Circuits 1 / 2 / 3 / 4)
1= separate
2= unique by circuits (1 – 2) / (3 – 4)
Pre-ventilation in cooling mode before compressor ON. Defines period while
the fans are activated at full speed before the (first) compressor activation
(only if FA01 = 4)
Outdoor fans working in cooling mode
Minimum outdoor fan speed in cooling mode
Defines the minimum oudoor fan speed during proportional regulation in
cooling mode. It is expressed as percentage (100% = 10V) .
Maximum outdoor fan speed
Defines the maximum outdoor fan speed during proportional regulation in
cooling mode. It is expressed as percentage (100% = 10V).
Proportional regulation
Condensing pressure/temperature value corresponding to the minimum
outdoor fan speed defined at FA07
Step regulation
1
st
STEP Set: Condensing pressure/temperature value corresponding to the
activation of the 1
st
outdoor fan step.