USER MANUAL – Release 1.2 of 01/01/2010 Page 34 of 191
4
th
STEP Set: Condensing pressure/temperature value corresponding to
the activation of the 4
th
outdoor fan step.
Condensing pressure/temperature differential between
activation and deactivation of the outdoor fan steps (ciruits
1/2).
Condensing pressure/temperature differential between
activation and deactivation of the outdoor fan steps (ciruits
3/4).
Outdoor fans working in heating mode – 3
rd
and 4
th
step
3
rd
STEP Set: Evaporating pressure value corresponding to the activation of
the 3
rd
outdoor fan step.
4
th
STEP Set: Evaporating pressure value corresponding to the activation of
the 4
th
outdoor fan step.
Evaporating pressure differential between activation and
deactivation of the outdoor fan steps (ciruits 1/2).
Evaporating pressure differential between activation and
deactivation of the outdoor fan steps (ciruits 3/4).
Outdoor fans working in defrost mode
Minimum outdoor fan speed in defrost mode.
Defines the minimum oudoor fan speed during proportional regulation in
defrost mode. It is expressed as percentage (100% = 10V).
Maximum outdoor fan speed in defrost mode.
Defines the maximum oudoor fan speed during proportional regulation in
defrost mode. It is expressed as percentage (100% = 10V).
Proportional regulation
Evaporating pressure value corresponding to the minimum outdoor fan speed
defined at FA16
Step regulation
1
st
STEP Set: Evaporating pressure value corresponding to the activation of the 1
st
outdoor fan
step.
Proportional regulation
Evaporating pressure value corresponding to the maximum outdoor fan speed
defined at FA17
Step regulation
2
nd
STEP Set: Evaporating pressure value corresponding to the activation of the 2
nd
outdoor
fan step.
Proportional regulation
Fans regulation proportional band in defrost mode
Defines the evaporating pressure proportional regulation band corresponding
to a variation from the minimum outdoor fan speed (FA16) to the night outdoor
fan speed (FA15).
Step regulation
Evaporating pressure differential between activation and deactivation of the
outdoor fan steps (ciruits 1/2).
Proportional regulation
CUT-OFF differential in defrost. Defines the evaporating pressure differential
for fan switch-off.
Step regulation
Evaporating pressure differential between activation and deactivation of the
outdoor fan steps (ciruits 3/4).
CUT-OFF over ride. Defines the evaporating pressure differential in which the
fan remains at minimum speed.
Night function speed. Defines the maximum fan speed for the proportional
regulation in defrost mode. It is expressed as percentage (100%=10V).
Outdoor fans working in defrost mode – 3
rd
and 4
th
step
3
rd
STEP Set: Evaporating pressure value corresponding to the activation of
the 3
rd
outdoor fan step.