USER MANUAL – Release 1.2 of 01/01/2010 Page 35 of 191
4
th
STEP Set: Evaporating pressure value corresponding to the activation of
the 4
th
outdoor fan step.
Evaporating pressure differential between activation and deactivation of the
outdoor fan steps (ciruits 1/2).
Evaporating pressure differential between activation and deactivation of the
outdoor fan steps (ciruits 3/4).
Antifreeze – Support – Boiler electric Heaters
Antifreeze /support heaters (air/air units) set-point in cooling mode
Defines the temperature below which the antifreeze heaters are activated in
cooling mode
Antifreeze / support heaters regulation band in cooling mode
Antifreeze / support heaters (air/air unit) set-point in heating mode
Defines the temperature below which the antifreeze heaters are activated in
heating mode
Antifreeze / support heaters regulation band in heating mode
Antifreeze / support heaters working mode during defrost cycle
0 = activated according to temperature control demand
1 = activated according to temperature control demand and during defrost
cycle
Temperature probe for controlling antifreeze alarm and antifreeze/support
heaters in cooling mode
0 = Disabled
1 = Evaporator inlet
2 = Evaporator outlet circuits 1 / 2
3 = Evaporator outlet circuits 3 / 4
4 = All evaporators outlet
5 = All evaporators outlet and common outlet
Temperature probe for controlling antifreeze/support heaters in heating mode
0 = Disabled
1 = Evaporator inlet
2 = Evaporator outlet circuits 1 / 2
3 = Evaporator outlet circuits 3 / 4
4 = All evaporators outlet
5 = All evaporators outlet and common outlet
Temperature probe for controlling condenser antifreeze heaters
0 = Disabled
1 = Common condenser water inlet
2 = Common condenser water inlet and condenser inlet circuits 1 / 2
3 = Common condenser water inlet and condenser inlet circuits 1 / 2
4 = Condenser water outlet probe circuits 1 / 2
5 = Condenser water outlet probe circuits 1 / 2
6 = All condenser water outlet probes
7 = All condenser water outlet probes and common outlet
Evaporator/condenser anti-freeze heaters working mode in the case of control
probe fault
0 = OFF
1 = ON
Antifreeze heaters activation in cooling/heating mode.
0 = Always OFF (cooling and heating)
1 = Cooling mode only depending on temperature control demand
2 = Heating mode only depending on temperature control demand
3 = Cooling and heating mode depending on temperature control demand
Antifreeze heaters activation in remote OFF/Standby mode.
0 = Always OFF
1 = ON depending on temperature control demand
Boiler function
0 = Disabled
1 = Integration mode
2 = Heating mode
External air temperature set point for Boiler heaters activation
External air temperature differential for Boiler heaters deactivation
Boiler heaters activation delay time