Boiler function working set point and differential
0 = Heating mode set point (ST04) and differential (ST08)
1 = Boiler function set point (Ar13) and differential (Ar14)
2 = The Working set point is the Heating set point increased by the Boiler
function set point (ST04+Ar17) and differential is the Boiler function one
(Ar18)
Boiler heaters function in heating mode
Boiler heaters function set point in heating mode
Boiler heaters function proportional band in heating mode
External air set point for compressors disabling in integration mode
External air differential for compressors disabling in integration mode
Defrost method
0 = Disabled
1 = According to evaporating pressure/temperature
2 = Start as defined on parameter dF28, end by maximum time
3 = Start as defined on parameter dF28, end by external contact
4 = By outdoor fans
Defrost start temperature/pressure
Defrost end temperature/pressure
Delay time between defrost on two different circuits
Compressors OFF time before defrost cycle start
Compressors OFF after defrost cycle end.
Delay time before defrost cycle start
Delay time between the reaching of the defrost conditions
(pressure/temperature) and the actual start of the defrost cycle.
Circuit n° 1 combined defrost cycle start temperature set point
After the expiration of the dF09 delay the actual defrost cycle occurs only
when the temperature sensed by the circuit 1 combined defrost temperature
probe drops below the dF10 limit.
Circuit n° 2 combined defrost cycle start temperature set point
Circuit n° 3 combined defrost cycle start temperature set point
Circuit n° 4 combined defrost cycle start temperature set point
Circuit n° 1 combined defrost cycle end temperature set point
The actual defrost cycle on circuit 1 terminates when the temperature sensed
by the combined defrost temperature probe exceeds the dF14 limit.
Circuit n° 2 combined defrost cycle end temperature set point
Circuit n° 3 combined defrost cycle end temperature set point
Circuit n° 4 combined defrost cycle end temperature set point
Forced activation of all capacity steps during defrost – circuit 1
0 = disabled
1 = enabled
Forced activation of all capacity steps during defrost – circuit 2
Forced activation of all capacity steps during defrost – circuit 3
Forced activation of all capacity steps during defrost – circuit 4
Delay between two compressors/capacity steps activation during defrost
mode
Ventilation enabling during defrost / dripping time
0 = disabled
1 = enabled only during defrost
2 = enabled in defrost / dripping
Condensing pressure/temperature level for outdoor fans forced activation
during defrost / dripping time.
The outdoor fans are activated during defrost / dripping time only if
condensing pressure is above the dF24 level. If this case occurs the
condensing pressure is the variable used for modulating the fan speed.