USER MANUAL – Release 1.2 of 01/01/2010 Page 43 of 191
Auxiliary proportional output n°4 differential
Auxiliary proportional output n°4 minimum value
Auxiliary proportional output n°4 maximum value
Low pressure alarm delay from digital/analogue input switching
Defines the low pressure alarm working with pump down enabled
0 = independent from pump down function
1 = disable the compressors until the end of the alarm condition
2 = enable the compressors start even if the alarm condition is still active
Low pressure alarm from analogue input set point
Low pressure alarm from analogue input differential
Maximum number of low pressure alarm (digital or analogue input)
occurrences per hour. If the number exceeds AL05 the alarm becomes
manual reset.
Reset is always manual if AL05 = 0
Reset is always automatic if AL05 = 60
Reset moves from automatic to manual if AL05 moves from 1 to 59
Low pressure alarm detection enabling in defrost mode
Low pressure alarm delay in defrost mode
Delay time between alarm condition occurrence and reaction by device
Low pressure alarm detection enabling in remote OFF remote
/ Stand-by mode
High pressure/temperature alarm from analogue input set point
High pressure/temperature alarm from analogue input differential
Maximum number of high pressure/temperature alarm (digital or analogue
input) occurrences per hour. If the number exceeds AL11 the alarm becomes
manual reset.
Reset is always manual if AL11 = 0
Reset is always automatic if AL11 = 60
Reset moves from automatic to manual if AL11 moves from 1 to 59
Delay on oil low pressure / low level alarm detection from compressor start
Delay on oil low pressure / low level alarm detection from digital input
switching.
After expiration of AL12 the unit waits further AL13 delay before detecting the
alarm
Maximum number of oil low pressure / low level alarm occurrences per hour
Reset is always manual if AL14 = 0
Reset is always automatic if AL14 = 60
Reset moves from automatic to manual if AL15 moves from 1 to 59
Oil low pressure / low level alarm enabling with compressor
OFF
Evaporator flow / supply fan overload alarm working mode
Delay on evaporator flow / supply fan overload alarm detection from water
pump / supply fan activation
Delay on evaporator flow / supply fan overload alarm activactivation before
moving from automatic to manual reset
Delay on evaporator flow / supply fan overload alarm activation from digital
input switching
Delay on evaporator flow / supply fan overload alarm automatic reset from
deactivation of the digital input (disabled if the alarm has turned to manual
reset)
Evaporator flow switch polarity detection enabling. If the polarity detection is
enabled the alarm occurs if the polarity doesn’t change after the pump start
regardless the polarity configuration.