Condenser flow alarm working mode
Condenser flow alarm working mode
0 = disabled
1 = enabled in cooling mode only
2 = enabled in heating mode only
3 = enabled both in cooling and heating mode
Delay on condenser flow alarm activation from water pump activation
Delay on condenser flow alarm activation before moving from automatic to
manual reset
Delay on condenser flow alarm detection from digital input switching
Delay on condenser flow alarm automatic reset from deactivation of the digital
input (disabled if the alarm has turned to manual reset)
Condenser flow switch polarity detection enabling. If the polarity detection is
enabled the alarm occurs if the polarity doesn’t change after the pump start
regardless the polarity configuration.
Compressors thermal overload alarm
Delay on compressor thermal overload alarm activation from compressor start
Maximum number of compressor thermal overload alarm occurrences per
hour
Reset is always manual if AL28 = 0
Reset is always automatic if AL28 = 60
Reset moves from automatic to manual if AL28 moves from 1 to 59
Compressor thermal overload alarm working mode
0 = blocks the individual compressor
1 = blocks the whole circuit
Compressor thermal overload alarm detection with compressor OFF
0 = Disabled
1 = Enabled
Compressor thermal overload alarm password value (see procedure)
Antifreeze / Low room air temperature / Low outlet air temperature alarm working in cooling mode
Minimum limit for antifreeze / low room air temperature / low outlet air
temperature alarm in cooling mode
Maximum limit for antifreeze /low room air temperature / low outlet air
temperature alarm in cooling mode
Antifreeze / low room air temperature / low outlet air temperature alarm set
point
Defines the temperature value below which the antifreeze / low room air
temperature / low outlet air temperature alarm is activated
Antifreeze / low room air temperature / low outlet air temperature alarm
differential
Antifreeze / low room air temperature / low outlet air temperature alarm delay
in cooling mode.
Delay on activation of the antifreeze / low room air temperature / low outlet air
temperature alarm from the occurrence of the alarm condition (temperature
below alarm set point)
Maximum number of antifreeze / low room air temperature / low outlet air
temperature alarms in cooling mode per hour.
Defines the maximum number of antifreeze / low room air temperature / low
outlet air temperature alarms per hour. When this number is exceeded the
alarm moves from automatic to manual reset.
Reset is always manual if AL37 = 0
Reset is always automatic if AL37 = 60
Reset moves from automatic to manual if AL37 moves from 1 to 59
Antifreeze alarm working in cooling mode
0 = Just switches the compressors off and shows the label without activating
buzzer and alarm relay
1 = switches the compressors off, shows the label and activates buzzer and
alarm relay
Antifreeze alarm working in heating mode
Minimum limit for antifreeze alarm in heating mode
Maximum limit for antifreeze alarm in heating mode
Antifreeze alarm set point in heating mode
Antifreeze / low room air temperature / low outlet air temperature alarm
differential in heating mode.
Antifreeze / low outlet air temperature alarm delay on unit start in heating
working mode
Warning
In case of alarm condition (control probe temperature lower than AL41) in
Stand-by or remote OFF status and AL43 not zero, if the unit is activated in
heating mode the antifreeze condition is neglected in order to allow the
compressors to start at least for the delay AL43 as the unit heats-up the water
or the air. On expiry of the AL43 delay time, if the antifreeze condition is still
active the AL44 counter is activated.