USER MANUAL – Release 1.2 of 01/01/2010 Page 45 of 191
Delay on activation of antifreeze / low room air temperature / low outlet air
temperature alarm from alarm condition occurrence during regular heating
mode.
Maximum number of antifreeze / low outlet air temperature alarms per hour in
heating mode.
When this number is exceeded the alarm moves from automatic to manual
reset.
Reset is always manual if AL45 = 0
Reset is always automatic if AL45 = 60
Reset moves from automatic to manual if AL45 moves from 1 to 59
Antifreeze alarm working in heating mode
0 = Just switches the compressors off and shows the label without activating
buzzer and alarm relay
1 = switches the compressors off, shows the label and activates buzzer and
alarm relay
Control probe for antifreeze alarm
Control probe in cooling mode
0 = Disabled
1 = Evaporator inlet
2 = Evaporator outlets 1 / 2
3 = Evaporator outlets 3 / 4
4 = All evaporator outlets
5 = All evaporator outlets and common outlet
Control probe in heating mode
0 = Disabled
1 = Evaporator inlet
2 = Evaporator outlets 1 / 2
3 = Evaporator outlets 3 / 4
4 = All evaporator outlets
5 = All evaporator outlets and common evaporators outlet
Condenser anti-freeze alarm temperature control probe
0 = Disabled
1 = Common condenser water inlet probe
2 = Common condenser water inlet probe and condenser inlet 1 / 2 probes
3 = Common condenser water inlet probe and condenser inlet 3 / 4 probes
4 = Condenser inlet 1 / 2 probes
5 = Condenser inlet 3 / 4 probes
6 = All condenser outlet probes
7 = All condenser outlet probes and common condenser outlet probe
Compressors high discharge temperature
Compressors high discharge temperature alarm set point
Compressors high discharge temperature alarm differential
Maximum number of compressors high discharge temperature alarm
occurrences per hour
When this number is exceeded the alarm moves from automatic to manual
reset.
Reset is always manual if AL52 = 0
Reset is always automatic if AL52 = 60
Reset moves from automatic to manual reset if AL52 moves from 1 to 59
Unit general block alarm n°1
Maximum number of unit general block alarm n°1 occurrences per hour
When this number is exceeded the alarm moves from automatic to manual
reset.
Reset is always manual if AL53 = 0
Reset is always automatic if AL53 = 60
Reset moves from automatic to manual reset if AL53 moves from 1 to 59
Delay on activation of unit general block alarm from digital input activation
Delay on deactivation of unit general block alarm from digital input
deactivation
Unit general block alarm n° 2
Unit general block alarm n° 2 working mode
0 = only notification (alarm relay and buzzer activated) always automatic reset
1 = the alarm blocks the unit. Alarm reset depends on the value of par. AL57
Maximum number of unit general block alarm n°2 occurrences per hour
When this number is exceeded the alarm moves from automatic to manual
reset.
Reset is always manual if AL57 = 0
Reset is always automatic if AL57 = 60
Reset moves from automatic to manual reset if AL57 moves from 1 to 59
Delay on activation of unit general block alarm from digital input activation
Delay on deactivation of unit general block alarm from digital input
deactivation
Evaporator inlet high temperature alarm