USER MANUAL – Release 1.2 of 01/01/2010 Page 46 of 191
Maximum number of evaporator water inlet high temperature probe alarm
occurrences per hour
Reset is always manual if AL60 = 0
Reset is always automatic if AL60 = 60
Reset moves from automatic to manual if AL60 moves from 1 to 59
Delay on activation of evaporator inlet high temperature alarm from
compressor activation
Evaporator inlet high temperature alarm set point
Evaporator inlet high temperature alarm differential
NTC / PTC probe controlling the evaporator inlet high temperature alarm
0 = function disabled
Alarm relay enabling in stand-by / remote OFF mode
Alarm history reset password value (see procedure)
Electronic thermostatic driver
Type of gas
1=R22
2=R407c
3=R134a
4=R410a
5=R404a
6=R507c
Configuration of the probes connected to the driver
Evaporating pressure measurement type
0 = Relative
1 = Absolute
Type of electronic expansion valve body:
0 = Bipolar
1 = Unipolar
Bipolar valve body model
0 = Custom
1 = Alco EX4 – EX5 – EX6
2 = Alco EX7
3 = Alco EX8
4 = Carel E2V*
5 = Carel E2V*P
6 = DANFOSS ETS – 25/50
7 = DANFOSS ETS – 100
8 = DANFOSS ETS – 250/400
9 = Sporlan SEI 0.5-20
10 = Sporlan SEI 30
11 = Sporlan SEH 50 – 250
Unipolar valve body model
0 = Custom
Driver model
0 = 1 valve
1 = 2 valves
Valve 1 working mode
0 = cooling only
1 = heating only
2 = cooling and heating
Valve 2 working mode
0 = cooling only
1 = heating only
2 = cooling and heating
Connection between driver 1 valve 1 and relevant circuit
0 = circuit 1
1 = circuit 2
2 = circuit 3
3 = circuit 4