XF6 Series Installation and Programming Guide Digital Monitoring Products
13
DRY CONTACT RELAY OUTPUTS
The panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model305relays in sockets
OUTPUT1and OUTPUT2and a Model431Output Harness on the OUT1-OUT2 6-pin header. Each relay provides one
SPDT set of contacts that can be operated by any of the functions listed below:
• Activation by zone condition—Steady, Pulsing, Momentary, and Follow
• Manual activation from the DMP LCD keypad menu
• Communication failure
• Fire Alarm, Fire Trouble, or Supervisory
Contact Rating
The Model305relay contacts are rated for1Amp at30VDC (allows 0.35power factor). You can connect auxiliary power
to the Relay Output1common terminal by installing the gray harness wire to Terminal7. Current draw for all connected
devices must not exceed the panel maximum current rating.
Model431Output Harness Wiring
The relay contacts are accessible by installing the DMP431Output Harness on the6-pin OUT1 OUT2header.
OUTPUT2uses the top three prongs, and OUTPUT1uses the bottom three prongs. The relay contacts must be
connected to devices located within the same room as the panel. The wire harness colors and contact locations are
shown below:
ANNUNCIATOR OUTPUTS
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or
conditions occurring on the system. Annunciator outputs do not provide voltage. Instead, they switch voltage from
another source to ground. The outputs can respond to any of the conditions listed in Dry Contact Relays. Maximum
voltage is30VDC at50mA.
Model300Harness Wiring
Access the open collector outputs by installing DMP300Harness on the4-pin OUTPUTS header. The output locations
are shown below. For listed applications, devices connected to the outputs must be located within the same room as the
panel.
Model860Relay Module
Connect a Model860Relay Module to the OUTPUTS header on the panel to provide relays for outputs3-6. Use these
relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various
functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power Terminal7.
The module includes one relay and provides three additional sockets for expansion of up to four relays. Mount
the860inside the panel enclosure using the3-hole pattern and plastic standos. Refer to the860Module Install Sheet
(LT-0484) as needed. Relay Contact Rating is 1Amp at30VDC (allows 0.35power factor).