XF6 Series Installation and Programming Guide Digital Monitoring Products
13
DRY CONTACT RELAY OUTPUTS
The panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model305relays in sockets
OUTPUT1and OUTPUT2and a Model431Output Harness on the OUT1-OUT2 6-pin header. Each relay provides one
SPDT set of contacts that can be operated by any of the functions listed below:
Activation by zone condition—Steady, Pulsing, Momentary, and Follow
Manual activation from the DMP LCD keypad menu
Communication failure
Fire Alarm, Fire Trouble, or Supervisory
Contact Rating
The Model305relay contacts are rated for1Amp at30VDC (allows 0.35power factor). You can connect auxiliary power
to the Relay Output1common terminal by installing the gray harness wire to Terminal7. Current draw for all connected
devices must not exceed the panel maximum current rating.
Model431Output Harness Wiring
The relay contacts are accessible by installing the DMP431Output Harness on the6-pin OUT1 OUT2header.
OUTPUT2uses the top three prongs, and OUTPUT1uses the bottom three prongs. The relay contacts must be
connected to devices located within the same room as the panel. The wire harness colors and contact locations are
shown below:
ANNUNCIATOR OUTPUTS
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or
conditions occurring on the system. Annunciator outputs do not provide voltage. Instead, they switch voltage from
another source to ground. The outputs can respond to any of the conditions listed in Dry Contact Relays. Maximum
voltage is30VDC at50mA.
Model300Harness Wiring
Access the open collector outputs by installing DMP300Harness on the4-pin OUTPUTS header. The output locations
are shown below. For listed applications, devices connected to the outputs must be located within the same room as the
panel.
Model860Relay Module
Connect a Model860Relay Module to the OUTPUTS header on the panel to provide relays for outputs3-6. Use these
relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various
functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power Terminal7.
The module includes one relay and provides three additional sockets for expansion of up to four relays. Mount
the860inside the panel enclosure using the3-hole pattern and plastic standos. Refer to the860Module Install Sheet
(LT-0484) as needed. Relay Contact Rating is 1Amp at30VDC (allows 0.35power factor).