Digital Monitoring Products XF6 Series Installation and Programming Guide
20
INITIALIZATION
Initialization
This function allows you to clear selected parts of the panel program back to the factory
defaults.
Clear All Memory
NO leaves existing programming intact then displays Clear All Codes.
YES clears all memory then displays Reset Panel. Reset the panel by shorting the reset
jumper and re-enter programming mode to continue.
Clear All Codes
NO leaves existing codes intact.
YES clears the user code and user profile memory and assigns user code number 99 to the
highest user number.
Clear Display Events Memory
NO leaves existing event memory intact.
YES clears the events memory.
Clear Zone Information
NO leaves existing zone information intact.
YES clears the zone information for all zones.
Clear Output Information
NO leaves existing output information intact.
YES clears all programmed output names and any output cuto assignment.
Clear Communication and Remote Options
NO leaves existing communication and remote options intact.
YES reset communication and remote options programming to factory defaults.
Set to Factory Defaults
NO leaves existing panel programming intact.
YES sets the panel’s programming back to factory default selections and clears all Device
Setup, System Options, and Remote Options programming from the panel. Selecting YES
does not clear the panel’s event memory, zone, user code information, or schedules.
INITIALIZATION
INIT ALL? NO YES
CODES? NO YES
EVENTS? NO YES
ZONES? NO YES
OUTPUTS? NO YES
COM/RMT? NO YES
DEFAULTS? NO YES

Table of Contents