SPECIFICATIONS SUMMARY
For a full list of compatible panel accessories, refer to "Accessory Devices".
POWER SUPPLY
Transformer— Input: 120V 60Hz, 1.3 Amp; Output: 28VAC 130VA
Standby Battery—24VDC (Two 12V batteries wired in series), 1.5Amps Max. charging current
Smoke and Auxiliary—24VDC output at 0.75Amp Max (not shared)
NAC Circuit 1 and NAC Circuit 2—24VDC at 2.5Amp Max
All combined circuits cannot exceed3.5Amps. All circuits are power limited except the red battery wire and AC terminal.
COMMUNICATION
Built-in network communication to SCS-1R and SCS-VR Receivers
Optional cellular communication to SCS-1R and SCS-VR Receivers
Can operate as a local panel
PANEL ZONES (24 VDC)
Sixpowered zones (3.3k EOL).
NAC BUS (24 VDC)
The two onboard NAC circuits support the following protocols:
DMP
Gentex
Wheelock
System Sensor
KEYPAD BUS (12 VDC)
You can connect the following supervised keypads and expansion modules to the Keypad Bus:
Alphanumeric keypads
Sixteen, eight, four, and single-zone expansion modules
Single zone detectors
LX-BUS (12 VDC)
You can connect the following devices to the LX-Bus connections provided on the panel. See Accessory Devices for
information about specific connections.
Sixteen, eight, four, and single-zone expansion modules
Relay output expansion modules
2W-BLX/2WT-BLX Addressable Smoke Detectors
OUTPUTS
The XF6 Series panel provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two
Model305relays, each rated1Amp at30VDC resistive (power limited sources only). A Model431Output Harness is
required to use these outputs.
The panel also provides four open collector outputs rated for50mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model300Output Harness is required to use these outputs.