SPECIFICATIONS SUMMARY
For a full list of compatible panel accessories, refer to "Accessory Devices".
POWER SUPPLY
Transformer— Input: 120V 60Hz, 1.3 Amp; Output: 28VAC 130VA
Standby Battery—24VDC (Two 12V batteries wired in series), 1.5Amps Max. charging current
Smoke and Auxiliary—24VDC output at 0.75Amp Max (not shared)
NAC Circuit 1 and NAC Circuit 2—24VDC at 2.5Amp Max
All combined circuits cannot exceed3.5Amps. All circuits are power limited except the red battery wire and AC terminal.
COMMUNICATION
• Built-in network communication to SCS-1R and SCS-VR Receivers
• Optional cellular communication to SCS-1R and SCS-VR Receivers
• Can operate as a local panel
PANEL ZONES (24 VDC)
Sixpowered zones (3.3k EOL).
NAC BUS (24 VDC)
The two onboard NAC circuits support the following protocols:
• DMP
• Gentex
• Wheelock
• System Sensor
KEYPAD BUS (12 VDC)
You can connect the following supervised keypads and expansion modules to the Keypad Bus:
• Alphanumeric keypads
• Sixteen, eight, four, and single-zone expansion modules
• Single zone detectors
LX-BUS (12 VDC)
You can connect the following devices to the LX-Bus connections provided on the panel. See Accessory Devices for
information about specific connections.
• Sixteen, eight, four, and single-zone expansion modules
• Relay output expansion modules
• 2W-BLX/2WT-BLX Addressable Smoke Detectors
OUTPUTS
The XF6 Series panel provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two
Model305relays, each rated1Amp at30VDC resistive (power limited sources only). A Model431Output Harness is
required to use these outputs.
The panel also provides four open collector outputs rated for50mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model300Output Harness is required to use these outputs.
Digital Monitoring Products XF6 Series Installation and Programming Guide