XF6 Series Installation and Programming Guide Digital Monitoring Products
39
A sensor reset is performed.
If the zone trips fewer than the specified times within one hour, the bypass trip counter
returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
Zone Retard Delay
When you select YES, the zone operates with the zone retard delay. The retard func tions
only in zone short condi tions. If you select NO, the zone operates without a retard delay.
The zone must re main shorted for the full length of the re tard de lay before the panel
recognizes its condition. If you select NO, the zone operates without a retard delay.
Fast Response
Select YES to provide a zone response time of 167ms. Select NO to provide a normal zone
response time of 500ms. Zones 500 to 999 have a fixed response time and do not display
this option.
Fire Panel Slave Input
This option is available on Fire Zones (FI) only and allows a fire zone the ability to provide
slave communication operation for a separate fire alarm control panel. If YES, this zone will
transmit a restoral immediately when restored by the fire panel being monitored. A sensor
reset is not required to generate the restoral message.
If NO, this zone will operate as a standard fire type zone and a sensor reset is required
before the zone will return to normal. Default is NO.
STOP
Stop
Save Programming
When any panel programming is changed, the stop routine must be run and “PLEASE
WAIT” must display on the keypad in order to save the programming changes.
At the STOP option, pressing any select key or area allows you to exit the Programmer
function of the panel. When selected, the panel performs an internal reset and exits the
RETARD NO YES
FAST RSP NO YES
FIRE PANEL SLAVE
INPUT: NO YES
STOP