XF6 Series Installation and Programming Guide Digital Monitoring Products
1
ABOUT THE PANEL
The DMP XF6 Series system consists of an alarm panel with a built-in communicator, an enclosure with built-in Graphic
Fire Command keypad, and a 28 VAC 130 VA transformer. A complete system can provide:
138 or 570 programmable inputs and outputs for commercial and industrial fire alarm service
Six onboard 24 V class B grounded zones, 2 NAC circuits
The powered zones have a reset capability to provide for2-wire smoke detectors, relays, or other latching devices.
Addressable smoke detectors and input modules round out the XF6 Series Series panel to deliver a truly flexible and
expansive fire detection and notification system. The Fire Alarm Control Panel is shipped ready to mount in a red steel
enclosure. It is not necessary to remove the panel PCB when installing the enclosure.
ZONE EXPANSION
The keypad bus features up to 64 zones (16 addresses with 4 zones per address)
Six 24 V zones on the terminal strip
Up to500zones are available using the on board LX-Bus connections. All 500 zones can be wireless.
OUTPUT EXPANSION
In addition to the two SPDT relays and four programmable open collector outputs on the panel, you can also connect up
to25programmable Model716Output Expansion Modules to each LX-Bus. These modules can provide an additional 100
or 500 programmable SPDT relays.