XF6 Series Installation and Programming Guide Digital Monitoring Products
47
SYSTEM TROUBLE or
SERVICE REQUIRED
There is a problem with one or more
components in the system.
Make sure the RESET jumper is removed
from the panel. Make sure there is not a
short or open condition on the green data
wire to the keypad. You may also need to
check that all of the keypads and expansion
modules on the bus are good.
SYSTEM BUSY
The system is performing another task with a
higher priority.
Wait a few moments for the system to
complete the task. Make sure the RESET
jumper is not on the panel. If the message
displays for a long period of time, the
processor could be locked up.
4-WIRE BUS TROUBLE
There is not a supervised device on the bus. Program a device to be supervised.
There is low voltage or an open yellow wire. Make sure all wires are connected.
Two devices share the same address.
Program one of the devices to a unique
address.
TRANSMIT FAIL
The panel has attempted to communicate
with the central station 10 times and has not
succeeded.
Verify your communication type, account
number, and phone number. Make sure the
telephone line is connected and working
properly.
NON-POLLED
ADDRESS
The device is not set to FIRE in Device Setup
during programming.
Program the device as FIRE in Device Setup.
ENTER CODE (to
enter Programming)
A lockout code has been programmed for the
panel.
Enter the lockout code.
WIRELESS TROUBLE
The panel is unable to communicate with the
wireless receiver.
Verify the receiver is properly connected to
the panel. Verify the correct House Code is
programmed in System Options. Satisfy the
front and/or rear tamper.
The wireless receivers tamper may be faulted.