DSE Model 5510 Autostart Control and Instrumentation System Operators Manual
057-015 5510 OPERATING MANUAL ISSUE 11 07/07/09 AM 30
4.5 ROCOF / VECTOR SHIFT
When configured to run in parallel with the mains (utility) supply, the module monitors for ROCOF /
Vector shift trips according to the module’s configuration settings. This is included within the module
and will detect failure of the mains supply during parallel operation with the generator.
NOTE:- This protection operates only when in parallel with the mains supply and is
disabled at all other times.
Should either of these alarms operate, the module will perform a controlled shutdown (electrical trip)
of the generator. This operation must be manually reset :
1) Press button. The engine will stop if it is still running and the alarm is cleared.
2) Activate digital input configured to “Clear ROCOF/Vector shift if this has been provided.
3) Press and button together and hold for 5 seconds. The ROCOF/Vector shift
instrument is displayed and all ‘peak hold’ values are reset, clearing the ROCOF/Vector shift
alarm.
Alarm
Mains ROCOF
Alarm
Mains Vector Shift
Alarm
Mains Decoupling
Low Frequency
Alarm
Mains Decoupling
High Frequency
Alarm
Mains Decoupling
Low Voltage
Alarm
Mains Decoupling
High Frequency
For details on activating and configuring the ROCOF/Vector shift protection you are referred to the
5xxx for Windows configuration software manual.