DSE Model 5510 Autostart Control and Instrumentation System Operators Manual
057-015 5510 OPERATING MANUAL ISSUE 11 07/07/09 AM 53
9.2.3 PLUG “C” 9 WAY
PIN
No
DESCRIPTION
20 Magnetic pickup screen
21 Magnetic Input positive. An AC signal from the magnetic pickup for speed sensing.
22 Magnetic Input negative. An AC signal from the magnetic pickup for speed sensing.
23 Electronic Engine ECU Screen
24 Electronic Engine ECU H. For connection to the Engine ECU CAN terminal H
25 Electronic Engine ECU L. For connection to the Engine ECU CAN terminal L
26 Multiset comms Link SCR
27 Multiset comms Link H. For connection to other DSE load share modules only.
28 Multiset comms Link L. For connection to other DSE load share modules only.
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that
the screen is earthed at one end ONLY.
NOTE:- Screened 120Ω
ΩΩ
Ω impedance cable specified for use with CAN must be used for
both the Electronic Engine link and the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω
ΩΩ
Ω impedance cable
suitable for CANbus use (DSE part number 016-030)
9.2.4 PLUG “D” 3 WAY
PIN
No
DESCRIPTION
29 RS485 SCREEN
30 RS485 B. For connection to other RS485 devices in a multidrop RS485 communications
system.
31 RS485 A. For connection to other RS485 devices in a multidrop RS485 communications
system.
NOTE:- Screened 120Ω
ΩΩ
Ω impedance cable specified for use with RS485 must be used.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω
ΩΩ
Ω impedance cable
suitable for CAN use (DSE part number 016-030)
9.2.5 PLUG “E” 5 WAY
PIN
No
DESCRIPTION
32 Governor output B. For connection to electronic speed governors for synchronising and load
sharing.
33 Governor output A. For connection to electronic speed governors for synchronising and load
sharing.
34 Unused
35 AVR output B. For connection to automatic voltage regulators for volts matching and VAr
sharing.
36 AVR output A. For connection to automatic voltage regulators for volts matching and VAr
sharing.
NOTE:- For details of connections to governors and AVRs, refer to the DSE Guide to
Synchronising Part 2.