Parameters
M-Max Series Adjustable Frequency Drive    MN04020003E—October 2013    www.eaton.com 65
Quickstart Wizard
The quick start assistant guides you in the quick 
configuration through all important settings that have to be 
made or that you should check for your application (see A in 
figure on Page 64). The parameters that are called during the 
process are listed in the table on Page 66, in the “Basic 
(Standard Drive)” column.
The process is run from parameter to parameter. Returning is 
not possible here.
When the quick configuration is completed, the frequency 
display M1.1 is activated automatically. Selecting the PAR 
main menu again enables you to call up the parameters of 
the quick configuration and then change them freely.
Besides the parameters of the quick configuration, system 
parameters S1.1 to S4.3 are also shown after the first 
setting.
P1.1 = 0 activates access to all parameters and the full 
functionality of all buttons of the keypad (free parameter 
definition, see B in the figure on Page 64).
This exits the quick configuration and the guided setup with 
the quick start assistant.
In the quick configuration, the OK button activates 
the individual parameter values and then moves on 
to the next parameter. Every parameter always 
shows the value that is set in alternating sequence. 
By actuating the OK button again, you activate the 
value (value flashes).
The arrow buttons have restricted 
functionality (change of parameter values 
and cursor control) in the quick start 
configuration.
OK