Appendix
04/10 MN04020001Z-EN
182
P5.2 314 / rw RO2 Signal
(Relay Output 2)
Like P5.1 85 3
P5.3
312 / rw DO Signal
(Digital Output 1)
Like P5.1 85 1
P5.4
315 / rw Frequency monitoring 1 0 = Deactivated
1 = 0.00 - P5.5 Hz
2 = P5.5 - P6.4 Hz
86 0
P5.5
316 / rw Frequency monitoring 1,
range
0.00 - P6.4 Hz 86 0.00
P5.6
346 / rw Frequency monitoring 2 0 = Deactivated
1 = 0.00 - P5.7 Hz
2 = P5.7 - P6.4 Hz
86 0
P5.7
347 / rw Frequency monitoring 2,
range
0.00 - P6.4 Hz 86 0.00
P5.8
1457 / rw Current monitoring 0.00 – P7.2 A 87 0.00
P5.9
1458 / rw DO logic
(control signal terminal 13)
0 = N/O
1 = N/C
87 0
P5.10
1331 / rw RO1 logic
(control signal terminal 22,
23).
Like P5.9 87 0
P5.11
1332 / rw RO2 logic
(control signal terminal 24,
25, 26).
Like P5.9 87 0
P5.12
1459 / rw DO, on delay 0.00 - 320.00 s 87 0.00
P5.13
1460 / rw DO, off-delay 0.00 - 320.00 s 87 0.00
P5.14
1461 / rw RO1, on delay 0.00 - 320.00 s 87 0.00
P5.15
1424 / rw RO1
Off-delay
0.00 - 320.00 s 87 0.00
P5.16
1425 / rw RO2, on delay 0.00 - 320.00 s 87 0.00
P5.17
1426 / rw RO2
Off-delay
0.00 - 320.00 s 87 0.00
Drives control
P6.1
125 / rw Control place 1 1 = Control signal terminals (I/O)
2 = Control unit (KEYPAD)
3 = Field bus (BUS)
88 1
P6.2
117 / rw Setpoint Source 0 = Fixed frequency (FF0)
1 = Operating unit (REF)
2 = Fieldbus (BUS)
3 = AI1 (analog setpoint 1)
4 = AI2 (analog setpoint 2)
5 = Motor potentiometer
88 3
P6.3 101 - rw Minimum frequency 0.00 - P6.4 Hz 89 0.00
P6.4
102 - rw Maximum frequency P6.3 - 320.00 Hz 89 50.00
P6.5
103 - rw Acceleration time (acc1) 0.1 - 3000 s 89 3.0
P6.6
104 - rw Deceleration time (dec1) 0.1 - 3000 s 89 3.0
P6.7
505 - rw Start function 0 = Ramp, acceleration
1 = Flying restart circuit
90 0
PNU
ID Access right Designation Value range Page FS
(P1.3)
User
setting
RUN ro/rw