04/10 MN04020001Z-EN
List of parameters
185
P8.13 715 - rw Underload protection
at zero frequency
10.0 - 150 % 98 10.0
P8.14
733 - rw Field bus error 0 = Deactivated
1 = Warning (AL 53)
2 = Error (F… 53)
stop function according to P6.8
98 2
P8.15 734 - rw Fieldbus,
interface error
0 = Deactivated
1 = Warning (AL 54)
2 = Error (F… 54 )
stop function according to P6.8
99 2
PID Controller
P9.1 163 / rw PID Controller 0 = Deactivated
1 = activated for drive control
2 = activated for external application
100 0
P9.2
118 / rw PID controllers, P
amplification
0.0 - 1000.0 % 100 100.0
P9.3
119 / rw PID controller, I reset time 0.00 - 320.00 s 100 10.00
P9.4
167 / rw PID controller, setpoint
input via operating unit
0.0 - 100.0 % 100 0.0
P9.5
332 / rw PI controller, setpoint
source
0 = Operating unit (P9.4)
1 = Field bus (option)
2 = AI1
3 = AI2
100 0
P9.6
334 / rw PID controller, actual value
(PV)
0 = Field bus (Option)
1 = AI1
2 = AI2
100 2
P9.7
336 / rw PID controller, actual value
limiting, minimum
0.0 - 100.0 % 100 0.0
P9.8
337 / rw PID controller, actual value
limiting, maximum
0.0 - 100.0 % 101 100.0
P9.9
340 / rw PID controller, controller
deviation
0 = not inverted
1 = inverted
101 0
P9.10
132 / rw PID controller, D rate time 0.00 - 10.0 s 101 0.00
P9.11
1431 / rw PID controller, output filter,
deceleration time
0.00 - 10.0 s 101 0.0
P9.12
1016 / rw Sleep mode, frequency 0.00 - P6.4 Hz 101 0.00
P9.13
1018 / rw Sleep mode,
wake up frequency
0.0 - 100.0 % 101 25.0
P9.14
1017 / rw Sleep mode,
deceleration time
0 - 3600 s 101 30
P9.15
1433 / rw Hysteresis,
upper limit
0.0 - 100.0 % 101 0.0
P9.16
1434 / rw Hysteresis,
lower limit
0.0 - 100.0 % 101 0.0
P9.17
1435 / rw PID controller,
max. system derivation
0.0 - 100.0 % 101 3.0
P9.18
1475 / rw PID controller,
scale setpoint display
0.1 - 32.7 102 1.0
PNU ID Access right Designation Value range Page FS
(P1.3)
User
setting
RUN ro/rw