6-10 EDMI Atlas Hardware Reference Manual
6-1
0
Figure 6-15 Connections for 3 element whole current
Figure 6-15 shows the normal connections for a whole current meter. The neutral
connection must be made, even if it is not connected to both 12 and 14. The VT/CT
links connect TB1 terminals 1 to 2, 4 to 5, 8 to 9, and 12 to 13 to 14. The links are fitted
under the main meter cover, discussed earlier in this chapter.
Figure 6-16 TB1 CT and VT connections for 3 element testing
Figure 6-16 shows the connection methods in 3 element (4 wire) mode when VT/CT
links are not fitted.