EPS Voltage Set: 120/240 | 127/220 three phase |
100/200 split phas
e | 120/208 | 110/220 | 115/230
Set the inverter output voltage.
EPS Frequency Set: 60H
z | 50Hz
Set the inverter output frequency.
AC Input Range: U
PS: 170-280 | APL: 90-280
Set the voltage range for AC Input. Switch over time will
typically, be slower when APL is selected.
PV Grid Off: D
isable | Enable
When enabled, provides off-grid functionality without using
battery backup. Note, AC output is only supplied by solar which
can cause output voltage instability due to fluctuating voltages from the solar modules. It is always
recommended to install a battery or battery bank to keep the inverter output voltage stable.
N-PE Connect (Inner): D
isable | Enable
Enable or disable the neutral ground bond inside the inverter. This is not a dynamic bond, meaning it
is only disabled or enabled.
PV Arc: D
isable | Enable
Enable detection of arcs on the PV input circuits and provides protection from PV circuit arcs.
PV Arc Fault Clear: Clear
Clears a fault detected due to arcs on the PV input circuit to the inverter.
RSD Enable: E
nable | Disable
Enable or disable the Rapid Shut Down feature.
(Page 2 / 3)
AC First: Start 00:00 - End 00:00
The time at which the inverter will use only AC to power
loads and uses all PV input to charge the battery.
The range is 00:00 – 23:59.