• AC Charge End Battery Voltage(V): Limit of voltage at which system will stop charging
batteries from AC. Range is 48 – 59V for end.
• AC Charge Start Battery SOC(%): Limit of SOC at which the system will start charging
batteries from AC. Range is 1 – 90% for start.
• AC Charge End Battery SOC(%):Limit of SOC at which the system will stop charging
batteries from AC. Range is 20 – 100% for end.
Generator Charge
• Generator Charge Type: Generator charging is set according to the battery voltage or
battery SOC.
• Generator Charge Battery Current(A): Set the generator battery charging current. Range is
0 – 250A.
• Generator Charge Start Battery Voltage(V): Starts the generator using dry contacts when
the battery voltage is below the generator charge battery voltage. Set according to the
battery requirements. Range is 39 – 57V
• Generator Charge End Battery Voltage(V): Stops generator using dry contacts when the
battery voltage is above generator charge end battery voltage is above the set battery
voltage. Set this according to the battery requirements. Range is 48 – 59VDC.
• Generator Charge Start Battery SOC(%): Starts the generator using dry contacts when
battery SOC% is below the generator charge start battery SOC%. Set this according to the
battery requirements. Range is 0 – 90%.
• Generator Charge End Battery SOC(%): Stops the generator using dry contacts when
battery SOC% is above the generator charge end battery SOC%. Set this according to the
battery requirements. Range is 20 – 100%.
• Max. Generator Input Power(W): Set the maximum generator input power. The inverter will
limit the power from the generator to 90% of the total generator capability to prevent
overloading. Range is 0 – 18,000 watts for a single inverter and 0 – 65,534 watts for
paralleled inverters.
• Generator Boost: Enable or disable the generator boost feature. Enable to allow the inverter
to pull supplemental power from both PV and battery whenever the generator power is not
sufficient to handle all loads.