FloChr: Floating
Charge Voltage
(Lead-Acid Only)
This setting allows the user to
set the Lead-Acid Battery
Float Charge Voltage.
Lead-Acid Floating Charge
Voltage:
Range: 50.0 – 56.0VDC
Default: 54.0VDC
9
Id:
Maximum
Discharge Current
This setting allows the user to
set the Maximum Discharge
Current.
Maximum Discharge Current:
Range: 10 140A
Default: 140A
10
TEOd: Discharge
Control Type
(Volt/SOC)
This setting allows the user
to select Voltage or SOC as
the trigger for battery
discharge.
11
CutOFF:
Cut o
Voltage/SOC
This setting allows the user to
set the cuto Voltage or SOC
based on the selection made in
Setting 10, TEOd.
Cuto Voltage:
40.0 On-Grid EOD Voltage
Default: 42V
Cuto SOC:
Range: 0 On-Grid EOD SOC%
Default: 15%