4 Operating From a Personal Computer
Operation Guide Flatpack MCU,
351300.013, v8-2006-07
53
4.10.3 Battery boost - Automatic boost charging
The automatic boost (equalize) charge function is developed to ensure a brief recharging time for the batteries after
discharge. Automatic boost must be enabled in the installation menu (see page 59) and the following parameters must
be set:
Threshold for boost to start (Ampere hour (discharge))
The auto boost will only start if the discharge of the batteries, in Ah, during mains failure or battery test was greater
than the threshold value. The auto boost threshold can be set from 0 to 1000 Ah. The auto boost is deactivated if the
threshold is 0 (default).
Max. boost duration (hours)
The maximum boost duration can be set from 0 to 20 hours. Duration set to 0 indicates that no maximum duration
limit is set. If the value is greater than 0, the boost will stop when the timer expires. This is independent of recharge
level.
Charge in percent of discharge (%)
Batteries can be charged from 100 % to 150 % of discharged Ah.