62 Chapter 6 Parameter Descriptions
F061 MS frequency 6
Range: 0.0Hz~Maximum frequency
40.00
F062 MS frequency 7
Range: 0.0Hz~Maximum frequency
50.00
F055~F062 defines the MS frequency for multi-speed operation.
TD3200
U
V
W
PE
M
COM
L
N
main control board
single-phase
AC supply
MCCB
k
1
X
3
X4
.
.
k
2
.
X5
.
k
3
Figure 6-11 Wiring for MS speed operation
In Figure 6-11, X3, X4 and X5 are MS terminals 1, 2, and 3 respectively.
Through the different logic combinations of K1, K2 and K3, the drive can
operate at 0~7 speed, see Table 6-1.
Table 6-1 Multi-speed Setthing
K3 K2 K1 Frequency setting
OFF OFF OFF MS frequency 0
OFF OFF ON MSfrequency 1
OFF ON OFF MS frequency 2
OFF ON ON MS frequency 3
ON OFF OFF MS frequency 4
ON OFF ON MS frequency 5
ON ON OFF MS frequency 6
ON ON ON MS frequency 7
6.5 Demo Functions
Demo mode is a cyclic operation of OD and CD. Press RUN key to start the
demo. The door is opened according to the operation curve. The drive starts
timing after the door is opened completely. When the time reaches the setting
TD3200 Variable Speed Drive for Elevator Door Control User Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Network Power TD3200 Series and is the answer not in the manual?

Emerson Network Power TD3200 Series Specifications

General IconGeneral
BrandEmerson Network Power
ModelTD3200 Series
CategoryControl Unit
LanguageEnglish