74 Chapter 6 Parameter Descriptions
In CD process, when the drive receives CD location limiting signal or when
the pulse count ed reaches the CD location limiting value, locking signal is
disabled and at the same time the catching torque reaches the setting of
F041, the drive will output signal 2 for complete CD.
The complete CD signal is disabled in demo mode, general-purpose drive
operation mode and OD process.
8: Locking signal output
Synchronously input/output locking signal
9: Door re-opening signal output
In door re-opening process, the drive outputs the door re-opening signal.
F107 Relay PC1 and PC2 contacts definition Range: 0~3
0: Neither PC1 or PC2 undergone NOT operation
1: NOT operation to PC1
2: NOT operation to PC2
3: NOT operation to both PC1 and PC2
If F107 is set at "0", both PA/PC1 and PA/PC2 are used as normally open
contacts
If F107 is set at "1", the relay PA/PC1 is used as normally closed contacts
and PA/PC2 normally open contacts
If F107 is set at "2", the relay PA/PC1 is used as normally open contacts and
PA/PC2 normally closed contacts
If F107 is set at "2", both PA/PC1 and PA/PC2 are normally closed contacts
F108 OD Priority Setting Range: 0~1
OD priority function setting
0: OD priority function enabled.
1: OD priority function disabled.
6.10 Display and Monitoring Functions
F109 Display selection for F109~F122
Range: 0, 1
【
0
】
F0109 decides whether to display F110~F122.
TD3200 Variable Speed Drive for Elevator Door Control User Manual