Chapter 5 Parameters Table 37
Para. Name Range Min.unit Default Mod.
F091 ASR integral time 2
0(no action),
0.032~32.00s
0.001s 0.400s
×
F092
ASR switching
frequency
0.00~400.0Hz 0.01Hz 5.00Hz
×
F093 Slip compensation gain
0 (reserved function),
50.0%~250.0%(for
accounting the slip
value)
0.1% 100.0%
×
F094 Motoring torque limiting
0.0~200.0%(rated
current)
0.1% 100.0%
×
F095 Braking torque limiting
0.0~200.0%( rated
current)
0.1% 100.0%
×
5.9 Digital I/O Function Parameters
Para. Name Range
Min.
unit
Default Mod.
F096
Display selection
F096~ F108
0: Not display
1: Display
10
○
F097 Function of X1
F098 Function of X2
F099 Function of X3
F100 Function of X4
0: No function (can be selected again)
1: External reset(RESET)input
2: Normally open input for optic signal
3: Normally closed input for optic signal
4: Normally open input for touching board
5: Normally closed input for touching
board
6: OD position control signal normally
open input
7: OD position control signal normally
closed input
8: CD position control signal normally
open input
9: CD position control signal normally
closed input
10: PG A-phase signal input(X1,X2)
11: PG B-phase signal input(X1,X2)
12: OD speed-shift contact normally open
1
0
×
TD3200 Variable Speed Drive for Elevator Door Control User Manual