The default setting is Downscale.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA
Output Fault Action to None. If you try to do this, the device will not accept the configuration.
2. If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level
as desired.
Postrequisites
CAUTION!
If you set mA Output Fault Action to None, be sure to set Digital Communications Fault Action to
None. If you do not, the output will not report actual process data, and this may result in
measurement errors or unintended consequences for your process.
Options for mA Output Fault Action and mA Output Fault
Level
Options for mA Output Fault Action and mA Output Fault LevelTable 10-3:
Option mA output behavior mA Output Fault Level
Upscale
Goes to the configured fault level Default: 21.5 mA
Range: 21.0 to 21.5 mA
Downscale (default) Goes to the configured fault level Default: 3.2 mA
Range: 3.2 to 3.6 mA
Internal Zero
Goes to the mA output level associated
with a process variable value of 0 (zero),
as determined by Lower Range Value and
Upper Range Value settings
Not applicable
None
Tracks data for the assigned process vari-
able; no fault action
Not applicable
10.3 Configure the discrete output
The discrete output is used to report specific meter or process conditions. The discrete
output parameters control which condition is reported and how it is reported. Depending
on your purchase option, your transmitter may have one discrete output or no discrete
outputs.
Integrate the meter with the control system