EasyManua.ls Logo

Emerson Micro Motion SGM Series - Chapter 7: Configure Process Measurement Using ProLink III

Emerson Micro Motion SGM Series
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Configure process measurement
using ProLink III
Topics covered in this chapter:
Configure specific gravity, molecular weight, or relative density parameters
using ProLink III
Configure temperature measurement using ProLink III
Configure the pressure input
Configure gas compressibility measurement using ProLink III
Configure base density calculations using ProLink III
Configure line density calculations using ProLink III
Configure energy content measurement using ProLink III
Set up concentration measurement using ProLink III
7.1 Configure specific gravity, molecular weight,
or relative density parameters using ProLink III
These parameters control the measurement of the core process variable.
Configure Damping using ProLink III (Section 7.1.1)
Configure the molecular weight of air using ProLink III (Section 7.1.2)
7.1.1
Configure Damping using ProLink III
ProLink III Device Tools > Configuration > Process Measurement > Specific Gravity > Damping
Device Tools > Configuration > Process Measurement > Molecular Weight > Damping
Device Tools > Configuration > Process Measurement > Relative Density > Damping
Overview
Damping controls the amount of damping that will be applied to the core process variable:
specific gravity, molecular weight, or relative density.
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Configure process measurement using ProLink III
Configuration and Use Manual 51

Table of Contents

Related product manuals