EasyManua.ls Logo

Emerson Micro Motion SGM Series - Page 163

Emerson Micro Motion SGM Series
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Status alerts, causes, and recommendations (continued)Table 14-2:
Alert number Alert title Possible causes Recommended actions
A100 mA Output 1
Saturated
The calculated mA output
value is outside the config-
ured range.
Check the settings of Upper Range Value and Low-
er Range Value. See Section 14.17.
Check process conditions. Actual conditions may
be outside the normal conditions for which the
output is configured.
Check for foreign material in the process gas or
fluid, coating, or other process problems.
Verify that the measurement units are configured
correctly for your application.
A101 mA Output 1
Fixed
The HART address is set to a
non-zero value, or the mA
output is configured to send
a constant value.
Check whether the output is in loop test mode. If
it is, unfix the output.
Exit mA output trim, if applicable.
Check the HART address. If the HART address is
non-zero, you may need to change the setting of
mA Output Action (Loop Current Mode).
Check whether the output has been set to a con-
stant value via digital communication.
A102 Drive Over-
range
The drive power (current/
voltage) is at its maximum.
Check the drive gain and the pickoff voltage. See
Section 14.22 and Section 14.23.
Check for foreign material in the process gas or
fluid, coating, or other process problems.
Check for fluid separation by monitoring the den-
sity value and comparing the results against ex-
pected density values.
Ensure that the sensor orientation is appropriate
for your application. Settling from a two-phase or
three-phase fluid can cause this alert.
A104 Calibration in
Progress
A calibration procedure is in
process.
Allow the procedure to complete.
A106 Burst Mode En-
abled
HART burst mode is ena-
bled.
No action required.
If desired, you can set Alert Severity Level to Ignore.
A107 Power Reset
Occurred
The transmitter has been re-
started.
No action required.
If desired, you can set Alert Severity Level to Ignore.
A113 mA Output 2
Saturated
The calculated mA output
value is outside the config-
ured range.
Check the settings of Upper Range Value and Low-
er Range Value. See Section 14.17.
Check process conditions. Actual conditions may
be outside the normal conditions for which the
output is configured.
Check for foreign material in the process gas or
fluid, coating, or other process problems.
Verify that the measurement units are configured
correctly for your application.
Troubleshooting
Configuration and Use Manual 155

Table of Contents

Related product manuals