EasyManua.ls Logo

Emerson Micro Motion SGM Series - Page 211

Emerson Micro Motion SGM Series
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Supply voltage and resistance requirementsFigure C-6:
A. External resistance (ohms)
B. Supply voltage VDC (volts)
C. Operating range
Note
4. To connect over a HART multidrop network:
a. Attach the leads from the signal converter to any point in the loop.
b. Add resistance as necessary to achieve at least one volt across the connection
points.
Important
HART/Bell 202 connections require a voltage drop of 1 VDC. To achieve this, add
resistance of 250–600 to the connection.
Using ProLink III with the transmitter
Configuration and Use Manual 203

Table of Contents

Related product manuals