Field Communicator connection to local HART loopFigure D-2:
A. Field Communicator
B. 250–600
Ω
resistance
C. External power supply
D. Transmitter with end-cap removed
3. To connect to a point in the HART multidrop network, attach the leads from the
Field Communicator to any point on the network.
Field Communicator connection to multidrop networkFigure D-3:
A. Field Communicator
B. Devices on the network
C. External power supply (may be provided by the PLC)
D. 250–600
Ω
resistance (may be provided by the PLC)
E. Master device
4. Turn on the Field Communicator and wait until the main menu is displayed.
Using the Field Communicator with the transmitter
210 Micro Motion
®
Gas Specific Gravity Meters (SGM)