100 Powerdrive F300 User Guide
Issue Number: 2
7 Analog output 1
8 Analog output 2
Terminal 7 default function
OL> Motor FREQUENCY output
signal
RFC> SPEED output signal
Terminal 8 default function Motor active current
Type of output
Bipolar single-ended analog voltage or
unipolar current
AOI [AO2] Mode controlled by... Pr
07.024 [07.024]
Operating in Voltage mode (default)
Voltage range ±10 V ±5 %
Maximum offset ±120 mV
Maximum output current ±20 mA
Load resistance 1 k Ω
Protection 20 mA max. Short circuit protection
Operating in current mode
Current ranges
0 to 20 mA ±5%, 20 to 0 mA ±5%
4 to 20 mA ±5%, 20 to 4 mA ±5%
Common to all modes
Resolution 10-bit
Sample / update period
250 µs (output will only change at update
the rate of the source parameter if slower)
9 0V common
Function
Common connection for all external
devices
21 0V common
Function
Common connection for all external
devices
22 Digital I/O 1
23 Digital I/O 2
24
Digital I/O 3
Terminal 22 default function DRIVE ACTIVE output
Terminal 23 default function DRIVE RESET input
Terminal 24 default function RUN FORWARD input
Type
Positive or negative logic digital inputs,
positive logic voltage source outputs
Input / output mode controlled by... Pr
08.031, Pr 08.032 and Pr 08.033
Operating as an input
Logic mode controlled by... Pr 08.029
Absolute maximum applied
voltage range
-3 V to +30 V
Impedance
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k Ω
Input thresholds 10 V ±0.8 V from IEC 61131-2, type 1
Operating as an output
Nominal maximum output current
100 mA (DIO1 & 2 combined)
100 mA (DIO3 & 24 V User Output
Combined)
Maximum output current
100 mA
200 mA (total including all Digital I/O)
Common to all modes
Voltage range 0 V to +24 V
Sample / Update period
2 ms (output will only change at the
update rate of the source parameter)
25 Digital Input 4
26
Digital Input 5
Terminal 25 default function
FIRE MODE ENABLE input
Terminal 26 default function
Analog INPUT 1 / INPUT 2 select
Type Negative or positive logic digital inputs
Logic mode controlled by... Pr
08.029
Voltage range 0 V to +24 V
Absolute maximum applied
voltage range
-3 V to +30 V
Impedance
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k Ω
Input thresholds 10 V ±0.8 V from IEC 61131-2, type 1
Sample / Update period 2 ms
27 Digital Input 6
Terminal 27 default function Unassigned input
Type Negative or positive logic digital inputs
Logic mode controlled by... Pr
08.029
Voltage range 0 V to +24 V
Absolute maximum applied
voltage range
-3 V to +30 V
Impedance
>2 mA @15 V from IEC 61131-2,
type 1,
6.6 k Ω
Input thresholds 10 V ±0.8 V from IEC 61131-2, type 1
Sample / Update period 2 ms

Table of Contents