Powerdrive F300 User Guide 85
Issue Number: 2
Table 4-13 Cable ratings (575 V)
Table 4-14 Cable ratings (690 V)
PVC insulated cable should be used.
Cable sizes are from IEC60364-5-52:2001 table A.52.C with correction
factor for 40°C ambient of 0.87 (from table A52.14) for cable installation
method as specified.
Installation class (ref: IEC60364-5-52:2001)
B1 - Separate cables in conduit.
B2 - Multicore cable in conduit.
C - Multicore cable in free air.
Cable size may be reduced if a different installation method is used, or if
the ambient temperature is lower.
N
The nominal output cable sizes assume that the motor maximum current
matches that of the drive. Where a motor of reduced rating is used the
cable rating may be chosen to match that of the motor. To ensure that
the motor and cable are protected against overload, the drive must be
programmed with the correct motor rated current.
A fuse or other protection must be included in all live connections to the
AC supply.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Maximum
Installation
method
Nominal Maximum
Installation
method
Nominal Maximum Nominal Maximum
05500039
0.75
1.5 B2
0.75
1.5 B2
16
16
16
1605500061
11
14 14
05500100
1.5 1.5
14 14
06500120
2.5
25 B2
2.5
25 B2
14
3
14
3
06500170
4
41010
06500220
6
61010
06500270
10
10
88
06500340 66
06500430
16
66
07500530
16
25 B2
16
25 B2
4
3
4
3
07500730
25 25
33
08500860
35
50 B2
35
50 B2 1 1 1 1
08501080
50 50
09501250
2 x 70
B2
2 x 35
B2 2 x 1
2 x 3
09501500 2 x 50 2 x 1
10502000
2 x 70
B2 2 x 70 B2 2 x 2/0 2 x 2/0
11502480
2 x 70
C
2 x 70
C
2 x 3/0 2 x 3/0
11502880
2 x 95 2 x 95
2 x 4/0 2 x 4/0
11503150
2 x 120 2 x 120
2 x 250 2 x 250
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Maximum
Installation
method
Nominal Maximum
Installation
method
Nominal Maximum Nominal Maximum
07600230
10
25 B2
10
25 B2
8
3
8
3
07600300 66
07600360 66
07600460
16 16
44
07600520
16 16
44
07600730
25 25
33
08600860
50
70 B2
50
70 B2
2
1/0
2
1/0
08601080
70 70
1/0 1/0
09601250
2 x 50
B2
2 x 35
B2
2 x 1 2 x 3
09601550
2 x 70
2 x 50 2 x 1/0 2 x 1
10601720
2 x 70
B2 2 x 70 B2
2 x 2/0 2 x 1/0
10601970
2 x 95
2 x 3/0 2 x 2/0
11602250
2 x 70
C
2 x 70
C
2 x 3/0 2 x 3/0
11602750
2 x 95
2 x 95
2 x 4/0 2 x 4/0
11603050
2 x 95
2 x 250 2 x 250