Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Onboard
PLC
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Powerdrive F300 User Guide 239
Issue Number: 2
Table 12-5 Losses @ 40°C (104° F) ambient with high IP insert installed
Model
Normal Duty
Drive losses (W) taking into consideration any current derating for the given conditions
2 kHz 3 kHz 4 kHz 6 kHz 8 kHz 12 kHz 16 kHz
200 V
03200066 93 95 99 104 113 122
03200080 100 102 107 113 122 133
03200110 123 126 133 140 158 157
03200127 128 124 122 118 98 84
04200180 145 151 151 146 142 146
04200250 215 205 194 189 187 199
5200300 244 249 262 274 298 328
400 V
03400034 80 84 94 103 123 137
03400045 88 92 102 105 110 134
03400062 84 85 89 92 109 134
03400077 114 117 122 135 172 203
03400104 118 134 155 173 221 267
03400123 118 134 155 173 221 267
04400185 105 114 132 153 197 207
04400240 101 111 131 152 197 207
05400300 170 173 182 194 223 268
575 V
05500039
05500061
05500100