Powerdrive F300 User Guide 285
Issue Number: 2
14.5.4 Type of conductors
Use copper conductors only.
14.5.5 Temperature rating of conductors
Use 75 °C rated conductors only.
14.5.6 Torque values
Torque values for field wiring terminals are provided in section
3.12.2 Terminal sizes and torque settings on page 65.
14.6 Environment
14.6.1 Environment
Drives are intended for operation in pollution degree 2 environments.
Drives are supplied as Open type.
Drives are classed as Enclosed Type 1 when installed with the intended
Type 1 terminal kit.
Devices are classed as Type 12 when installed in a Type 12 enclosure.
14.7 Mounting
14.7.1 Surface mounting
All drives are suitable for Surface mounting. Mounting instructions are
given in section 3.5.1 Surface mounting on page 32.
14.7.2 Bookcase mounting
In order to minimise the width of the installation, devices may be
mounted side by side with or without airspace between them.
14.7.3 Tile mounting
Frame sizes 3, 4 and 5 are suitable for tile mounting. The drive is
mounted sideways with the side panel against the mounting surface. Tile
mounting kits are available.
14.7.4 Through-hole mounting
All models may be through hole mounted. When through-hole mounted,
inside a Type 12 enclosure, the high-IP insert (where provided) and the
Type 12 sealing kit must be used in order to prevent ingress of dust and
water. Refer to section 3.5.2 Through-panel mounting on page 39.
14.8 Listed Accessories
14.8.1 Option modules
The following option modules and accessories are UL listed:
Open Type:
Not all option modules are compatible with all drive models.
14.9 cUL Marking requirements
14.9.1 External transient suppression
Model numbers 07500530, 07500730, 8500860, 8501080 rated 575 V
require external transient suppression in order to comply with cUL
approval requirements:
14.9.2 Opening of branch-circuit protection
SI-PROFINET RT SI-I/O
SI-Ethernet SD-Card Adaptor
SI-DeviceNet KI-485 Adaptor
SI-CANopen KI-HOA keypad RTC
SI-PROFIBUS
Transient surge suppression shall be installed on the line side
of this equipment and shall be rated 575 Vac (phase to
ground), 575 Vac (phase to phase), suitable for overvoltage
protection category III, and shall provide protection for a rated
impulse withstand voltage peak of 6 kV and a clamping
voltage of maximum 2400 V.
The opening of the branch-circuit protective device may be
an indication that a fault has been interrupted. To reduce the
risk of fire or electric shock, current-carrying parts, and other
components of the controller should be examined and
replaced if damaged.