EasyManua.ls Logo

Emerson Powerdrive F300 - Option 3 for Achieving IP54 Size 9 to 11 through Panel Mounting; Environmental Considerations; Power Losses from the Front of the Drive When Through-Panel Mounted

Emerson Powerdrive F300
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Onboard
PLC
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Powerdrive F300 User Guide 55
Issue Number: 2
Figure 3-45 Option 3 for achieving IP54 (NEMA 12) size 9 to 11 through panel mounting
The guidelines in Table 3-9 should be followed.
For detailed information regarding IP54 (NEMA 12) Through Panel Mounting see Figure 3-30 Through-panel mounting the size 9A on page 42,
Figure 3-31 Through-panel mounting the size 9E and 10 on page 43 and Figure 3-32 Through-panel mounting the size 11E on page 44.
Table 3-9 Environmental considerations
When designing an IP65 (NEMA 12) enclosure (Figure 3-37 Example of IP65 (sizes 3 to 8) layout on page 50), consideration should be made to the
dissipation from the front of the drive.
Table 3-10 Power losses from the front of the drive when through-panel mounted
Enclosure
rear wall
Sealing
brackets
(6 places)
6xM5
screws with
sealing braclkets
Environment Fan Comments
Clean Standard
Dry, dusty (non-conductive) Standard Regular cleaning recommended. Fan lifetime may be reduced.
Dry, dusty (conductive) Standard / IP54 Regular cleaning recommended. Fan lifetime may be reduced.
IP54 compliance IP54 Regular cleaning recommended.
NOTE
Frame size Power loss
3 50 W
4 75 W
5 100 W
6 100 W
7 204 W
8 347 W
9A/9E/10E/11E 480 W
NOTE

Table of Contents

Other manuals for Emerson Powerdrive F300

Related product manuals