282 Powerdrive F300 User Guide
Issue Number: 2
13.5 Internal / Hardware trips
Trips {HF01} to {HF20} are internal faults that do not have trip numbers.
If one of these trips occurs, the main drive processor has detected an
irrecoverable error. All drive functions are stopped and the trip message
will be displayed on the drive keypad. If a non permanent trip occurs this
may be reset by power cycling the drive. On power up after it has been
power cycled the drive will trip on Stored HF. Enter 1299 in mm.000 to
clear the Stored HF trip.
13.6 Alarm indications
In any mode, an alarm is an indication given on the display by alternating
the alarm string with the drive status string on the first row and showing
the alarm symbol in the last character in the first row. If an action is not
taken to eliminate any alarm except "Auto Tune and Limit Switch" the
drive may eventually trip. Alarms are not displayed when a parameter is
being edited, but the user will still see the alarm character on the upper
row.
Table 13-6 Alarm indications
13.7 Status indications
Table 13-7 Status indications
Table 13-8 Option module and NV Media Card and other status
indications at power-up
13.8 Programming error indications
Following are the error message displayed on the drive keypad when an
error occurs during programming of drive firmware.
Table 13-9 Programming error indications
Alarm string Description
Motor Overload
Motor Protection Accumulator (04.019) in the drive
has reached 75.0 % of the value at which the drive
will trip and the load on the drive is >100 %.
Drive Overload
Drive over temperature. Percentage Of Drive
Thermal Trip Level (07.036) in the drive is greater
than 90 %.
Auto Tune
The autotune procedure has been initialized and an
autotune in progress.
Upper row
string
Description
Drive
output
stage
Inhibit
The drive is inhibited and cannot be run.
The Safe Torque Off signal is not applied to
Safe Torque Off terminals or Pr 06.015 is
set to 0
Disabled
Ready
The drive is ready to run. The drive enable
is active, but the drive inverter is not active
because the final drive run is not active
Disabled
Stop The drive is stopped / holding zero speed. Enabled
Run The drive is active and running Enabled
Supply Loss Supply loss condition has been detected Enabled
Deceleration
The motor is being decelerated to zero
speed / frequency because the final drive
run has been deactivated.
Enabled
dc injection The drive is applying dc injection braking Enabled
Trip
The drive has tripped and no longer
controlling the motor. The trip code
appears in the lower display
Disabled
Under
Voltage
The drive is in the under voltage state
either in low voltage or high voltage mode
Disabled
Heat The motor pre-heat functions inactive Enabled
Phasing
The drive is performing a ‘phasing test on
enable’.
Enabled
First row
string
Second row string Status
Booting Parameters Parameters are being loaded
Drive parameters are being loaded from a NV Media Card
Booting User Program User program being loaded
User program is being loaded from a NV Media Card to the drive
Booting
Option
Program
User program being loaded
User program is being loaded from a NV Media Card to the option
module in slot X
Writing To NV Card
Data being written to NV Media
Card
Data is being written to a NV Media Card to ensure that its copy of the
drive parameters is correct because the drive is in Auto or Boot mode
Waiting For Power System Waiting for power stage
The drive is waiting for the processor in the power stage to respond
after power-up
Waiting For Options Waiting for an option module
The drive is waiting for the Options Modules to respond after power-up
Uploading
From
Options Loading parameter database
At power-up it may be necessary to update the parameter database
held by the drive because an option module has changed or because
an applications module has requested changes to the parameter
structure. This may involve data transfer between the drive an option
modules. During this period ‘Uploading From Options’ is displayed
Error
String
Reason Solution
Error 1
There is not enough drive
memory requested by all
the option modules.
Power down drive and remove
some of the option modules
until the message disappears.
Error 2
At least one option module
did not acknowledge the
reset request.
Power cycle drive
Error 3
The boot loader failed to
erase the processor flash
Power cycle drive and try
again. If problem persists,
return drive
Error 4
The boot loader failed to
program the processor
flash
Power cycle drive and try
again. If problem persists,
return drive
Error 5
One option module did not
initialize correctly. Option
module did not set Ready
to Run flag.
Remove faulty option module.