Table 7-7 Dyneo LSRPM 3600 rpm motors
* From firmware version 01.12.xx.xx onwards, the rated current from the motor nameplate is entered into Pr 05.007 / Pr 00.046 and will be updated
automatically to the sensorless value after an autotune.
Table 7-8 Dyneo LSRPM 4500 rpm motors
* From firmware version 01.12.xx.xx onwards, the rated current from the motor nameplate is entered into Pr 05.007 / Pr 00.046 and will be updated
automatically to the sensorless value after an autotune.
Table 7-9 Dyneo LSRPM 5500 rpm motors
* From firmware version 01.12.xx.xx onwards, the rated current from the motor nameplate is entered into Pr 05.007 / Pr 00.046 and will be updated
automatically to the sensorless value after an autotune.
LSRPM Motor model
Motor rated current
(nameplate value)
Pr 00.046
*
Sensorless motor
rated current after
autotune
*
Switching
frequency
Pr 00.041
Ke
Pr 00.047
Motor Thermal
Time Constant
Pr 00.053
A A kHz V/1000 rpm s
3600 LSRPM 132M 17.6 kW 33.0 33.7 8 103 1050
3600 LSRPM 132M 22 kW 39.4 41.2 8 103 1050
3600 LSRPM 132M 26 kW 48.0 48.0 8 106 1050
3600 LSRPM 160MP 34 kW 63.0 63.0 8 106 1050
3600 LSRPM 160MP 41 kW 77.0 77.0 8 107 1050
3600 LSRPM 160LR 49 kW 91.0 91.0 8 110 1050
3600 LSRPM 200L1 70 kW 129 137 4 100 900
3600 LSRPM 200L1 85 kW 162 162 4 100 900
3600 LSRPM 200LU2 115 kW 217 232 4 103 900
3600 LSRPM 225SG 132 kW 250 250 4 103 1150
3600 LSRPM 250SE1 165 kW 330 330 4 96 1150
3600 LSRPM 250SE1 190 kW 350 360 4 106 1150
3600 LSRPM 280SD1 240 kW 420 429 4 108 1150
LSRPM Motor model
Motor rated current
(nameplate value)
Pr 00.046
*
Sensorless motor
rated current after
autotune
*
Switching
frequency
Pr 00.041
Ke
Pr 00.047
Motor Thermal
Time Constant
Pr 00.053
A A kHz V/1000 rpm s
4500 LSRPM 132M 18.6 kW 35.0 35.0 8 86 1050
4500 LSRPM 132M 23 kW 44.0 44.0 8 84 1050
4500 LSRPM 132M 27 kW 51.0 51.0 8 83 1050
4500 LSRPM 160MP 35 kW 67.0 67.0 8 90 1050
4500 LSRPM 160MP 44 kW 81.0 81.0 8 92 1050
4500 LSRPM 160LR 52 kW 97.0 97.0 8 86 1050
4500 LSRPM 200L1 65 kW 130 142 8 82 900
4500 LSRPM 200L1 80 kW 160 172 8 82 900
4500 LSRPM 200L1 100 kW 200 200 8 79 900
4500 LSRPM 200L2 120 kW 230 230 8 82 900
4500 LSRPM 200LU2 135 kW 258 260 8 84 900
4500 LSRPM 225SR2 150 kW 262 281 8 91 900
LSRPM Motor model
Motor rated current
(nameplate value)
Pr 00.046
*
Sensorless motor
rated current after
autotune
*
Switching
frequency
Pr 00.041
Ke
Pr 00.047
Motor Thermal
Time Constant
Pr 00.053
A A kHz V/1000 rpm s
5500 LSRPM 132M 18.6 kW 35.0 35.0 8 74 1050
5500 LSRPM 132M 23 kW 44.0 44.0 8 74 1050
5500 LSRPM 132M 27 kW 52.0 52.0 8 77 1050
5500 LSRPM 160MP 35 kW 67.0 67.0 8 76 1050
5500 LSRPM 160MP 44 kW 82.0 82.0 8 77 1050
5500 LSRPM 160LR 52 kW 97.0 97.0 8 77 1050
5500 LSRPM 200L1 70 kW 140 141 8 68 900
5500 LSRPM 200L1 85 kW 170 170 8 64 900
5500 LSRPM 200L1 100 kW 210 210 8 64 900
5500 LSRPM 200L2 140 kW 265 296 8 67 900