3.12.2 Terminal sizes and torque settings
Table 3-21 Drive power terminal data
Table 3-22 Drive control and relay terminal data
Table 3-23 Plug-in terminal block maximum cable sizes
Table 3-24 External EMC filter terminal data
To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified tightening torques for the power and ground
terminals. Refer to the following tables.
Powerdrive
F300 frame
size
AC and motor terminals DC and braking Ground terminal
Recommended Maximum Recommended Maximum Recommended Maximum
3 and 4
Plug-in terminal block T20 Torx (M4) T20 Torx (M4) / M4 Nut (7 mm AF)
0.7 N m (0.5 lb ft) 0.8 N m (0.6 lb ft) 2.0 N m (1.4 Ib ft) 2.5 N m (1.8 Ib ft) 2.0 N m (1.4 Ib ft) 2.5 N m (1.8 Ib ft)
5
Plug-in terminal block T20 Torx (M4) / M4 Nut (7 mm AF) M5 Nut (8 mm AF)
1.5 N m (1.1 lb ft) 1.8 N m (1.3 lb ft) 1.5 N m (1.1 Ib ft) 2.5 N m (1.8 Ib ft) 2.0 N m (1.4 Ib ft) 5.0 N m (3.7 Ib ft)
6
M6 Nut (10 mm AF) M6 Nut (10 mm AF) M6 Nut (10 mm AF)
6.0 N m(4.4 Ib ft) 8.0 N m (6.0 Ib ft) 6.0 N m(4.4 Ib ft) 8.0 N m (6.0 Ib ft) 6.0 N m(4.4 Ib ft) 8.0 N m (6.0 Ib ft)
7
M8 Nut (13 mm AF) M8 Nut (13 mm AF) M8 Nut (13 mm AF)
12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft) 12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft) 12 N m (8.8 Ib ft) 14 N m (10.0 Ib ft)
8 to 11
M10 Nut (17 mm AF) M10 Nut (17 mm AF) M10 Nut (17 mm AF)
15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft) 15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft) 15 N m (11.1 Ib ft) 20 N m (14.8 Ib ft)
Model Connection type Torque setting
All Plug-in terminal block 0.5 N m (0.4 lb ft)
Model size Terminal block description Max cable size
All
11 way control connectors
1.5 mm
2
(16 AWG)
2 way relay connector
2.5 mm
2
(12 AWG)
3
6 way AC power connector
6 mm
2
(10 AWG)
4
5
3 way AC power connector
3 way motor connector
8 mm
2
(8 AWG)
6
2 way low voltage power
24 V supply connector
1.5 mm
2
(16 AWG)
7
8
9A/9E
10E/11E
CT part
number
Power
connections
Ground
connections
Max cable
size
Max torque
Ground
stud size
Max torque
4200-1132
50 mm
2
(1/0 AWG)
8.0 N m
(6.0lb ft)
M10
18 N m
(13.3 lb ft)
4200-0672
4200-1972
95 mm
2
(3/0 AWG)
20 N m
(14.8 lb ft)
4200-1662
4200-0122
16 mm
2
(6 AWG)
2.3 N m
(1.7 lb ft)
M6
5.0 N m
(3.7 lb ft)
4200-0252
1.8 N m
(1.4 lb ft)
4200-0272
4200-0312
4200-0402
4200-3230
4 mm
2
(12 AWG)
0.8 N m
(0.59 lb ft)
M5
2.5 N m
(1.8 lb ft)
4200-3480
4 mm
2
(12 AWG)
0.8 N m
(0.59 lb ft)
M5
4200-2300
16 mm
2
(6 AWG)
2.3 N m
(1.70 Ib ft)
M6
5.0 N m
(3.7 lb ft)
4200-4800
4200-3690
4200-3021 TBC TBC
M10
TBC
4200-4460 TBC
25 N m
(18.4 lb ft)
TBC
4200-1660 TBC TBC TBC
4200-2210 TBC
25 N m
(18.4 lb ft)
TBC
4200-0400 TBC TBC
M12
25 N m
(18.4 lb ft)
4200-0690 TBC TBC