12.1.22 Protective ground cable ratings
Table 12-22 Protective ground cable ratings
12.1.23 Input line reactor specification for size 9E, 10E and 11E
Table 12-23 Size 9E and10 Model and Line reactor part number
* Natural cooling.
** May represent a more economic solution where operating temperature and cooling requirements are observed.
*** May represent a more economic solution when operating below 420 A.
Figure 12-1 Input line reactor dimensions
Table 12-24 Input line reactor ratings
* Natural cooling.
** May represent a more economic solution where operating temperature and cooling requirements are observed.
If symmetrical fault current exceeds 38 kA then a line reactor with a higher inductance must be used, consult the supplier of the drive.
Input phase
conductor size
Minimum ground conductor size
10 mm
2
Either 10 mm
2
or two conductors of the same cross-sectional area as the input phase conductor.
> 10 mm
2
and 16 mm
2
The same cross-sectional area as the input phase conductor
> 16 mm
2
and 35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the input phase conductor
A separate line reactor (INLXXX) of at least the value shown in Table 12-24 and Table 12-23 must be used with size 9E, 10E and 11E.
Failure to provide sufficient reactance could damage or reduce the service life of the drive.
Size Drive model Inductor model Line reactor part number
9E
09202160, 09202660, 09402210, 09402660
INL 401 4401-0181
INL 401W** 4401-0208
09501250, 09501500, 09601720, 09601970 INL 601 4401-0183
10E
10203250, 10203600, 10403200, 10403610
INL 402 4401-0182
INL 402W** 4401-0209
10502000, 10601720, 10601970 INL 602 4401-0184
11E
11404370 INL 403L*** 4401-0274
11404370, 11404870, 11405070 INL 403* 4401-0259
11502480, 11502880, 11503150, 11602250, 11602750, 11603050 INL 603* 4401-0261
Part
number
Model
Current Inductance
Overall
width (W)
Overall
depth (D)
Overall
height (H)
Weight
Max
ambient
temp
Min
airflow
Maximum
losses
Quantity
required
A μHmmmmmmkg°Cm/sW
4401-0181 INL 401 245 63 240 190 225 32 50 1 148 1
4401-0182 INL 402 339 44 276 200 225 36 50 1 205 1
4401-0208 INL 401W** 245 63 255 235 200 27 40 3 1
4401-0209 INL 402W** 339 44 255 235 200 27 40 3 1
4401-0274 INL 403L* 420 30 300 216 264 57 40 0 1
4401-0259 INL403* 557 30 300 216 264 57 40 0 1
4401-0183 INL 601 145 178 240 190 225 33 50 1 88 1
4401-0184 INL 602 192 133 276 200 225 36 50 1 116 1
4401-0261 INL 603* 331 93 300 216 264 58 40 0 1