Pr 00.022 determines whether the reference is uni-polar or bi-polar as
follows:
Open-loop
If the preset reference has been selected (see Pr 00.005), the speed at
which the motor runs is determined by these parameters.
RFC-A / RFC-S
If the speed feedback (Pr 03.002) exceeds this level in either direction,
an overspeed trip is produced. If this parameter is set to zero, the
overspeed threshold is automatically set to 120 % x
SPEED_FREQ_MAX.
Open-loop
Refer to Pr 00.024 to Pr 00.026.
This parameter shows the number of the data block last transferred from
a SMARTCARD to the drive.
* Only a value of 3 or 4 in this parameter is saved.
If Pr 00.030 is equal to 1 or 2, this value is not transferred to the
EEPROM or the drive. If Pr 00.030 is set to a 3 or 4 the value is
transferred.
For further information, please refer tosection 9 NV Media Card
Operation on page 162.
Pr Value Pr string Comments
-4 4-20 mA Low
4-20 mA low value on
current loss (1)
-3 20-4 mA Low
20-4 mA low value on
current loss (1)
-2 4-20 mA Hold
4-20 mA hold at level before
loss on current loss
-1 20-4 mA Hold
20-4 mA hold at level before
loss on current loss
0 0-20 mA
120-0 mA
2 4-20 mA Trip 4-20 mA trip on current loss
3 20-4 mA Trip 20-4 mA trip on current loss
4 4-20 mA
520-4 mA
6Volt
7 Therm Short Cct
Temperature Measurement
Input With Short Circuit
Detection
8 Thermistor
Temperature Measurement
Without Short Circuit
Detection
9 Therm No Trip
Temperature Measurement
Input With No Trips
00.022 {01.010} Bipolar Reference Enable
RW Bit US
OL
Ú
OFF (0) or On (1)
Ö
OFF (0)RFC-A
RFC-S
Pr 00.022 Function
0 Unipolar speed/frequency reference
1 Bipolar speed/frequency reference
00.024 {01.021} Preset Reference 1
RW Num US
OL
Ú
±VM_SPEED_FREQ_
REF Hz / rpm
Ö
0.0 Hz / rpmRFC-A
RFC-S
00.025 {01.022} Preset Reference 2
RW Num US
OL
Ú
±VM_SPEED_FREQ_
REF Hz / rpm
Ö
0.0 Hz / rpmRFC-A
RFC-S
00.026 {01.023} Preset Reference 3 (OL)
00.026 {03.008} Overspeed Threshold (RFC)
RW Num US
OL
Ú
±VM_SPEED_FREQ_
REF Hz
Ö
0.0 Hz / rpm
RFC-A
Ú
0 to 40000 rpm
RFC-S
00.027 {01.024} Preset Reference 4 (OL)
RW Num US
OL
Ú
±VM_SPEED_FREQ_
REF Hz
Ö
0.0
RFC-A
Ú Ö
RFC-S
00.029 {11.036} NV Media Card Data Previously Loaded
RO Num NC PT US
OL
Ú
0 to 999
Ö
0RFC-A
RFC-S
00.030 {11.42} Parameter Cloning
RO Txt NC US*
OL
Ú
None (0), Read (1),
Program (2), Auto (3),
Boot (4)
Ö
None (0)RFC-A
RFC-S
Pr
String
Pr
value
Comment
None 0 Inactive
Read 1 Read parameter set from the NV Media Card
Program 2
Programming a parameter set to the NV Media
Card
Auto 3 Auto save
Boot 4 Boot mode